Laserfiche WebLink
FARRINGTON <br /> Ira=r, AIR QUALITY SERVICES <br /> Air Handling Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: AHU-01/B-27 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 600 CFM <br /> Model Number VDDF Actual Max Airflow 600 CFM <br /> Serial Number R23K01761 Max Diff.SP 0.40 in.wc <br /> Box Inlet Size 08/06 Min Design CFM 160 CFM <br /> K Factor 2.14/2.15 Actual Min Airflow 170 CFM <br /> Min Diff.SP 0.03 in.wc <br /> Design Reheat Airflow 440 CFM <br /> Actual Reheat Airflow 415 CFM <br /> Reheat Diff.SP 0.65 in.wc <br /> AHU-01/B-27 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 10 Flowhood 1.00 200 <br /> Outlet-02 CD 10 Flowhood 1.00 200 <br /> Outlet-03 CD 10 Flowhood 1.00 200 <br /> Totals: - - - - 600 0 0 0 <br /> SYSTEM/UNIT: AHU-01/B-28 Tested By: Eric Liles <br /> Date: 6/13/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 900 CFM <br /> Model Number VDDF Actual Max Airflow 865 CFM <br /> Serial Number R23K01766 Max Diff.SP 0.32 in.wc <br /> Box Inlet Size 10/8 Min Design CFM 270 CFM <br /> K Factor 2.0/2.0 Actual Min Airflow 264 CFM <br /> Min Diff.SP 0.03 in.wc <br /> Design Reheat Airflow 630 CFM <br /> Actual Reheat Airflow 638 CFM <br /> Reheat Diff.SP 0.44 in.wc <br /> AHU-01/B-28 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM _ _ <br /> Outlet-01 CD 12 Flowhood 1.00 900 900 900 100 <br /> Totals: - - - - 900 900 900 100 <br /> Farrington Air Quality Services <br />