Jose Villagomez <br /> Cascade Cleanup and Restoration, Inc. <br /> Plan Check Number: B2106-009, First Building Review <br /> October 12, 2021 <br /> 5. Continuing with the previous comment, if the CS-PF braced wall is to be utilized at the walls <br /> adjacent to the garage door, then the garage door header on Sheet S-3 should be specified as <br /> continuous and should meet the minimum required size specified in Detail 1/No Sheet Number <br /> titled Portal Framing. <br /> 6. See Sheet A-1 and Page 4 of the APA Wall Bracing Calculator Project Report. Braced walls <br /> should be specified at the location of Wall Line 1 as shown in the braced wall design. <br /> 7. See Section R602.10.8 and Detail 4/A-5. Detail should specify a continuous rim or band joist or <br /> blocking. A note should specify that all connections to be per Table R602.3(1) shown on Sheet <br /> unnumbered. <br /> 8. Provide general structural notes including but not limited to: <br /> a. Specify all design load values, including dead, live, snow, wind, and soil bearing <br /> values. <br /> b. Specify maximum design concrete strength, concrete sack mix and reinforcing bar <br /> grade. <br /> 9. See Sheet S-2. Plans specify an option for TJI floor joists but provided calculations do not show <br /> a design for TJI joists. Provide a design calculation for the TJI floor joists or remove option note <br /> from the plans. <br /> 10. See Sheet A-1, A-2, S-1, and S-2. Plans should show stair framing, connections, and supporting <br /> member sizes for the stairs located in the house, garage, and porch. R106.1.1 <br /> 11. See Sheet S-3, note 4. Plans should provide a detail of the ladder framing located at gable ends <br /> and any specify connections. <br /> 12. See Sheet S-3. Plans should specify gable end bracing capable to resist out of plane wall forces <br /> at gable end truss. R502.11.2, R106.1.1 <br /> 13. See Detail 10/A-5. Detail should specify minimum penetration into the connecting member. It <br /> appears that some of the screws are not penetrating the connecting member. See connection <br /> between knee brace and post. <br /> 14. See Sheet A-2. It appears that a guardrail is located adjacent to the stairway. Plans should <br /> provide a detail specifying the requirements per Section R312.1. The plans should include <br /> details for the construction of the guards. The guards, connections, and structural framing <br /> supporting the guards should be designed for a 200-pound load applied in any direction and <br /> guard in-fill components should be designed to withstand a horizontally applied normal load of <br /> 50 pounds on an area equal to 1 square foot. See loading requirements for guard in IRC Table <br /> 301.5. <br /> 3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 4 of 5 <br />