s dio19 archil-ecl-s ■i <br /> t:2o6.466.ua5 www.studioigarchitects.cam ■ <br /> 207 i/7 first ave s,suite 300,seats a wa 98104 <br /> 3.Sheet G0.00 lists the addition of a fire alarm system. It is unclear if this is a voluntary or mandatory. <br /> See comments above and clarify if this is related to one of the indicated occupancy changes. <br /> RESPONSE: We are not including the fire alarm system as it is not required. Please see clarification <br /> under the description of work on the cover sheet G0.00 <br /> 4. The door between the dining area and the kitchen does not comply with the requirements for <br /> accessible doorways per ICC Al 17.1-09 Figure 404.2.3.2 and should be revised. Note that if a latch <br /> and closer are provided, the door requires side clearances for both directions. See IBC Section <br /> 1101.2. <br /> RESPONSE: The doorway between the dining area and the kitchen has been revised to comply <br /> with ICC A117.01-09. Please see sheet A2.02 for references. <br /> 5. The restroom should specify an exhaust fan. <br /> RESPONSE: We have revised the reflected ceiling plan legend to include "Restroom Exhaust Fan" <br /> instead of"Restroom Fan"for clarification. Please see sheet A3.00 <br /> We trust that the information presented is sufficient to address the comments above. If you have <br /> any questions regarding this letter or the resubmitted drawings or if you require additional <br /> information, please call us at (206) 466 1225. <br /> Sincerely, <br /> Zeyu Li <br /> Studio 19 Architects <br /> 21z <br />