1 I 2 I 3 I 4 I 5 I 6 17 I 8 I 9 I 10 <br /> DIV 26 - LEGEND CIRCUITING DESIGNATIONS GENERAL SYMBOL <br /> POWER WHERE A PANEL NAME AND CORRESPONDING CIRCUIT ARE CALLED OUT ADJACENT TO A RECEPTACLE,LUMINAIRE,OR MISC LOAD,THAT LOAD SHALL BE SCALE CONDUIT&WIRE TAG <br /> CIRCUITED TO THE CORRESPONDING PANELBOARD CIRCUIT BREAKER.CONDUIT AND WIRE FOR CIRCUIT SHALL BE 3/4"CONDUIT WITH(2)12 AWG AND(1)12 SECTION LETTER (REFER TO CONDUIT <br /> DELTA CONNECTION -es RECEPTACLE,SINGLE WITH SWITCH AWG GND,UNLESS OTHERWISE NOTED;IF FURTHER THAN 70',PHASE AND GROUND WIRE SHALL BE UPSIZED TO 10 AWG TO ACCOUNT FOR VOLTAGE DROP. SECTION AND WIRE SCHEDULE) <br /> MOTOR,SINGLE-PHASE ® HARDWIRED SEE EXAMPLES BELOW: 0 FAULT CURRENT TAG <br /> (3 PH,SYM AMPS) <br /> A ® MOTOR,THREE-PHASE �s RECEPTACLE,SWITCHED DUPLEX RECEPTACLE- P1-2 SHEET WHERE <br /> P1-2 X KEY NOTE A <br /> PANELBOARD OR POWER SOURCE NAME="P1„ SECTION IS TAKEN <br /> VV�/V CIRCUIT NUMBER OF POWER SOURCE="2" FROM <br /> TRANSFORMER � DROP CORD,SINGLE CONVENIENCE OUTLET,3-WIRE, IF PHoro,ARROW <br /> Nr GROUNDING TYPE,20A,W/912 CONDUCTORS IN FLEXIBLE DENOTES DIRECTION <br /> WYE CONNECTION CORD(CENTER LINE OF OUTLET:6'-6"[1981mm]AFF.MINIMUM). LUMINAIRE: TAKEN <br /> PANELBOARD OR POWER SOURCE NAME="PP3" PP3-4 SECTION LETTER <br /> EARTH GROUND � ELECTRICAL STRIP MOLD(OUTLETS ON 2'-0"[610mm] CIRCUIT NUMBER OF POWER SOURCE="4" r L1 FIGURE PHOTO <br /> - - - DETAIL NUMBER <br /> CENTERS OR AS DESIGNATED ON DRAWINGS),MTD TYP LUMINIARE TAG NAME,REFERENCE LUMINAIRE SCHEDULE_"L1" a L1 L1 ��a XXX XXX <br /> SHEET WHERE <br /> ��rE a �rl <br /> O JUNCTION BOX 3'-6"[1067mm]AFF OR AS INDICATED. LIGHTING CONTROL SWITCH LEG="a" L _ _ _ _ _ _ _ _ _ _ PP3-4 SECTION IS TAKEN SHEET WHERE DETAIL <br /> ALL LUMINAIRES IN SAME ROOM ARE CIRCUITED TO SAME CIRCUIT=IPF�- FROM IS TAKEN FROM <br /> Pe PULL BOX $u SWITCH ALL LUMINAIRES WITHIN DASHED BOX ARE CIRCUITED TO SAME CIRCUIT=PP3-4 <br /> F=FUSED SWITCH K=KEY OPERATED DETAIL NUMBER <br /> SWITCH,MULTIPOSITION L=LOCK LM=LOW VOLTAGE MASTER [PANEULB <br /> C LOAD HEAT PUMP FACP DETAIUPLAN NUMBER <br /> M=MANUAL MOTOR STARTING MC=MOMENTARY CONTACT OARD OR POWER SOURCE NAMEPP-7 �PP-7 XXMP=MOTOR SNAP WITH PILOT LIGHT P=WITH PILOT LIGHT C NUMBER OF POWER SOURCE_"T' SHEET <br /> ON WHICH <br /> DETAIL/PLAN <br /> SWITCH,SINGLE BREAK (THERMAL TYPE) APPEARSDETAIL <br /> NORMALLY CLOSED RELAY CONTACT PB=PUSH BUTTON STATION RC=REMOTE CONTROL DETAILAREA--------- -___-_J <br /> WP=WEATHER PROOF <br /> T NORMALLY OPEN RELAY CONTACT X=EXPLOSION PROOF <br /> LIGHTING <br /> B FUSE WITH RATING SWITCH,CEILING MOUNTED PULL B <br /> �1 CIRCUIT BREAKER $n SWITCH(#SUBSCRIPT AS INDICATED BELOW): <br /> DRAWOUT AIR CIRCUIT BREAKER BLANK=SINGLE POLE 2=DOUBLE POLE <br /> 3=THREE-WAY 4=FOUR-WAY <br /> O RELAY;NUMBER INDICATES RELAY TYPE D=DIMMER K=KEY OPERATED <br /> 50=INSTANTANEOUS OVER CURRENT OR RATE-OF-RISE LV=LOW VOLTAGE P=WITH PILOT LIGHT <br /> 51=AC-TIME OVER CURRENT LM=LOW VOLTAGE MASTER RC=REMOTE CONTROL <br /> 67=AC-DIRECTIONAL OVER CURRENT PB=PUSH BUTTON STATION WP=WEATHER PROOF <br /> 86=LOCKING OUT T=TIMER OPERATED Mo=OCCUPANCY SENSOR <br /> DISCONNECT SWITCH,FUSED x=LUMINAIRE SWITCH ZONE(ANY LOWER CASE LETTER APPLIES) - <br /> ❑ DISCONNECT SWITCH,UNFUSED EMERGENCY NORMAL X=DENOTES LUMINAIRE TAG NAME <br /> m STARTER,COMBINATION WITH DISCONNECT SWITCH <br /> m #XX RECESSED DOWNLIGHT FIXTURE <br /> STARTER OR MOTOR CONTROLLER <br /> O GENERATOR,POWER LIGHT FIXTURE,RECESSED,2'x4' <br /> BATTERY X X <br /> C CAPACITOR �X �X LIGHT FIXTURE,RECESSED,1'x4' C <br /> O METER X X LIGHT FIXTURE,RECESSED,1'x8' <br /> O AMMETER <br /> O VOLTMETER LIGHT FIXTURE,RECESSED,2'x2' <br /> O X X <br /> WATTMETER <br /> O WATT-HOUR METER LIGHT FIXTURE,SURFACE MOUNTED,2'x4' <br /> X X <br /> MOTOR <br /> �X �X LIGHT FIXTURE,SURFACE MOUNTED,1'x4' <br /> ITT I TRANSFORMER,PLAN <br /> LADDER CABLE TRAY <br /> X O X LIGHT FIXTURE,SURFACE MOUNTED,1'x8' <br /> PANELBOARD,FLUSH MOUNTED LIGHT FIXTURE,SURFACE MOUNTED,2'x2' <br /> PANELBOARD,SURFACE MOUNTED 101 101X <br /> RECEPTACLE,DUPLEX,20A,125V 'X �sX STRIP LIGHTING,4'LONG <br /> D D <br /> RECEPTACLE,DUPLEX ON EMERGENCY POWER,20A,125V X=� *1 XE::;= & LIGHT FIXTURE,WALL MOUNTED <br /> 4) RECEPTACLE,DUPLEX WITH GROUND FAULT CIRCUIT X X <br /> INTERRUPTER,20A,125V X Xl STREET LIGHT WITH BRACKET <br /> 4 RECEPTACLE,QUADRUPLEX,20A,125V <br /> X O �X LIGHT POLE,ONE LUMINAIRE <br /> � RECEPTACLE,SINGLE,20A,125V <br /> ® RECEPTACLE,DUPLEX FLOOR MOUNTED 0C- LIGHT POLE,TWO LUMINAIRES <br /> RECEPTACLE,DUPLEX CEILING MOUNTED *X X LIGHT POLE,POST TOP MOUNT LUMINAIRE <br /> j CONDUIT OR EQUIPMENT TO BE REMOVED <br /> CONDUIT CONCEALED IN WALL,CEILING,UNDER FLOOR, X X LIGHTING WALL PACK,EXTERIOR BUILDING <br /> IN FLOOR SLAB,OR ROUTED UNDERGROUND ♦ <br /> CONDUIT CONCEALED WHERE POSSIBLE,OTHERWISE 1Q 1 EXIT SIGN,WALL MOUNTED WITH DIRECTIONAL ARROWS AND <br /> EXPOSED FACES AS SHOWN <br /> -UAIll\, EXTRA-HARD USAGE FLEXIBLE CORD tet EXIT SIGN,CEILING MOUNTED WITH DIRECTIONAL ARROWS AND <br /> E FACES AS SHOWN E <br /> 4b FLEXIBLE CONDUIT <br /> 9 EXIT SIGN,ABOVE DOOR,CEILING MOUNTED <br /> --------0 CONDUIT TURNED UP OR TOWARD <br /> LIGHT FIXTURE,BOLLARD <br /> E) CONDUIT TURNED DOWN OR AWAY <br /> LIGHT TRACK WITH HEADS AS SHOWN <br /> CONDUIT CAPPED <br /> os ALL INTERIOR AREAS TO HAVE MANUAL"ON"/AUTO OFF LIGHTING <br /> CONDUIT 3/4"C,3#12 PHASE,1#12 N,8 1#12 GND UNLESS x CONTROL WITH THE USE OF DUAL TECHNOLOGY OCCUPANCY <br /> P1-1,3,5 SHOWN OTHERWISE.(EXAMPLE SHOWN:TO PANEL P1, SENSORS.EXCEPT WHERE A WALL SWITCH OCCUPANCY SENSOR <br /> CIRCUIT 1,3,5).LONG TICK FOR NEUTRAL WIRE;ONE SHORT IS NOTED. <br /> TICK FOR EACH PHASE WIRE;GROUND SIZED PER NEC.NOTE <br /> THAT A SECOND SHORT TICK FOR LUMINAIRES IS FORA PE x PHOTO ELECTRIC SENSOR <br /> TRAVELER WIRE. <br /> CONDUIT HOME RUN-SEE CONDUIT AND WIRE SCHEDULE Ds X SHALL BE CEILING MOUNTED.DAYLIGHT SENSOR FOR DAYLIGHT HARVESTING CONTROL.SENSOR <br /> � A RECEPTACLE,SPECIAL PURPOSE;SHADED <br /> INDICATES EMERGENCY POWER POWER PACK FOR COMPLEX LIGHTING CONTROL."X"DENOTES THE <br /> PP <br /> A=120V,20A,1 PHASE,2-POLE,3W,NEMA 5-20R. x LIGHTING ZONE. <br /> F B=208V,20A,1 PHASE,2-POLE,3W,NEMA 6-20R. # METERING POINT F <br /> C=120V,30A,1 PHASE,2-POLE,3W,NEMA 5-30R. �( u <br /> D=208V,30A,1 PHASE,2-POLE,3W,NEMA 6-30R. LIGHTING,ONE HEAD EMERGENCY BATTERY POWER <br /> E=208V,60A,1 PHASE,3-POLE,4W,NEMA 14-60R. <br /> F=208V,30A,3 PHASE,4-POLE,5W,NEMA L21-30R. LIGHTING,TWO HEAD EMERGENCY BATTERY POWER <br /> H=2 8V,0A,3 PHASE,3 POLE,4W,NEMA 15-60R. LIGHTING,THREE HEAD EMERGENCY BATTERY POWER THESE ARE GENERAL LEGENDS. NOT ALL SYSMBOL MAY BE SHOWN. <br /> ® MAIN LUGS REFERENCE PLANS FOR ALL UTILIZED SYMBOLS. <br /> Drawing Title Phase Project Title L14(02300166 <br /> ect Number <br /> STAMP CONSULTANT/DISCIPLINE ARCHITECT/ENGINEER OF RECORD ELECTRICAL LEGENDS CONSTRUCTION SET CNC AT SKILLS CENTER <br /> DISCIPLINE: A/E: <br /> WASH�"o ELECTRICAL ENGINEERING Building Number <br /> SPEES DESIGN BUILD RAH AEC <br /> tiP TO 23830 PACIFIC HIGHWAY S.SUITE 203 210 Shadow Lane NE <br /> n <br /> KENT,WA 98032 Olympia,WA 98506 �O RA <br /> � Locatio 9001 AIRPORT RD EVERETT,WA 96204-1423 Drawing Number <br /> 5561 <br /> Mukilteo School District Issue Date Checked Drawn E-002 <br /> CONSTRUCTION SET os/os/zoza Po��SFOis <br /> NALE �oG SPEESDESGNBUILD ° Y <br /> mS/ N RESPONSIVE ACCOUNTABLE HUMBLE t 0_O 09/06/2024Boo SGG/WNM JFO/JGD 030E 07 <br /> Revisions: Date: <br /> 1 I 2 I 3 I 4 I 5 I 6 I 7 18 I 9 I 10 <br />