ZONE FCU-1
<br />Conditions at Time of Space Cooling Peak
<br />Conditions at Time of Space Heating Peak
<br />Peak Time (Mo/D/H:M)
<br />7/21 18:00:00
<br />Peak Time (Mo/D/H:M)
<br />12/21 24:00:00
<br />Outside DB / WB / HR
<br />75.9 °F / 60.7 °F /
<br />55.9 gr/lb
<br />Outside DB / WB / HR
<br />25.4 °F / 19.1 °F
<br />/ 5.9 gr/lb
<br />Zone DB / RH / HR
<br />75.0 °F / 46.3 % /
<br />60.6 gr/lb
<br />Zone DB / RH / HR
<br />70.0 °F / 7.8 %
<br />/ 8.5 gr/lb
<br />Time
<br />Percent
<br />Time
<br />Percent
<br />Instant
<br />Delay
<br />of
<br />Instant
<br />Delay
<br />of
<br />Sensible
<br />Sensible Latent
<br />Total
<br />Total
<br />Sensible
<br />Sensible Latent
<br />Total
<br />Total
<br />(Btu/h)
<br />(Btu/h) (Btu/h)
<br />(Btu/h)
<br />(%)
<br />(Btu/h)
<br />(Btu/h) (Btu/h)
<br />(Btu/h)
<br />(%)
<br />Roof
<br />0
<br />1,059 0
<br />1,059
<br />2.5
<br />Roof
<br />0
<br />-749 0
<br />-749
<br />6.5
<br />Other Roof
<br />0
<br />0 0
<br />0
<br />0.0
<br />Other Roof
<br />0
<br />0 0
<br />0
<br />0.0
<br />Glass
<br />4,660
<br />26,253 0
<br />30,913
<br />72.0
<br />Glass
<br />-4,223
<br />0 0
<br />-4,223
<br />36.4
<br />Door
<br />0
<br />0 0
<br />0
<br />0.0
<br />Door
<br />0
<br />0 0
<br />0
<br />0.0
<br />Wall
<br />0
<br />1,011 0
<br />1,011
<br />2.4
<br />Wall
<br />0
<br />-1,017 0
<br />-1,017
<br />8.8
<br />Below -Grade Wall
<br />0
<br />0 0
<br />0
<br />0.0
<br />Below -Grade Wall
<br />0
<br />0 0
<br />0
<br />0.0
<br />Other Wall
<br />0
<br />0 0
<br />0
<br />0.0
<br />Other Wall
<br />0
<br />0 0
<br />0
<br />0.0
<br />Partition
<br />0
<br />-2,475 0
<br />-2,475
<br />-5.8
<br />Partition
<br />0
<br />265 0
<br />265
<br />-2.3
<br />Exterior Floor
<br />0
<br />0 0
<br />0
<br />0.0
<br />Exterior Floor
<br />0
<br />0 0
<br />0
<br />0.0
<br />Interior Floor
<br />0
<br />0 0
<br />0
<br />0.0
<br />Interior Floor
<br />0
<br />0 0
<br />0
<br />0.0
<br />Slab
<br />0
<br />-1,144 0
<br />-1,144
<br />-2.7
<br />Slab
<br />0
<br />-106 0
<br />-106
<br />0.9
<br />Other Floor
<br />0
<br />0 0
<br />0
<br />0.0
<br />Other Floor
<br />0
<br />0 0
<br />0
<br />0.0
<br />Infiltration
<br />28
<br />0 -89
<br />-61
<br />-0.1
<br />Infiltration
<br />-5,450
<br />0 0
<br />-5,652
<br />48.7
<br />Envelope Subtotal
<br />4,688
<br />24,704 -89
<br />29,303
<br />-
<br />Envelope Subtotal
<br />-9,673
<br />-1,607 0
<br />-11,482
<br />-
<br />People
<br />4,329
<br />0 4,030
<br />8,359
<br />19.5
<br />People
<br />0
<br />0 0
<br />0
<br />0.0
<br />Lights
<br />1,423
<br />0 0
<br />1,423
<br />3.3
<br />Lights
<br />0
<br />0 0
<br />0
<br />0.0
<br />Miscellaneous Loads
<br />3,984
<br />299 0
<br />4,283
<br />10.0
<br />Miscellaneous Loads
<br />0
<br />0 0
<br />0
<br />0.0
<br />Internal Subtotal
<br />9,736
<br />299 4,030
<br />14,065
<br />-
<br />Internal Subtotal
<br />0
<br />0 0
<br />0
<br />-
<br />RA (All Other)
<br />0
<br />0 0
<br />0
<br />0.0
<br />RA (All Other)
<br />0
<br />0 0
<br />0
<br />0.0
<br />DOA Direct to Zone
<br />0
<br />0 0
<br />0
<br />0.0
<br />DOA Direct to Zone
<br />0
<br />0 0
<br />0
<br />0.0
<br />Ceiling
<br />0
<br />0 0
<br />0
<br />0.0
<br />Ceiling
<br />0
<br />0 0
<br />0
<br />0.0
<br />Refrigeration
<br />0
<br />0 0
<br />0
<br />0.0
<br />Refrigeration
<br />0
<br />0 0
<br />0
<br />0.0
<br />Service Water
<br />0
<br />0 0
<br />0
<br />0.0
<br />Service Water
<br />0
<br />0 0
<br />0
<br />0.0
<br />HVAC Equipment Losses
<br />0
<br />0 0
<br />0
<br />0.0
<br />HVAC Equipment Losses
<br />0
<br />0 0
<br />0
<br />0.0
<br />Adj Air Transfer Heat
<br />0
<br />0 0
<br />0
<br />0.0
<br />Adj Air Transfer Heat
<br />0
<br />0 0
<br />0
<br />0.0
<br />Sizing Factor Correction
<br />0
<br />0 0
<br />0
<br />0.0
<br />Sizing Factor Correction
<br />0
<br />0 0
<br />0
<br />0.0
<br />Time Delay Correction
<br />0
<br />-448 0
<br />-448
<br />-1.0
<br />Time Delay Correction
<br />0
<br />-116 0
<br />-116
<br />1.0
<br />Grand Total
<br />14,424
<br />24,556 3,940
<br />42,920
<br />100.0
<br />Grand Total
<br />-9,673
<br />-1,723 0
<br />-11,598
<br />100.0
<br />RA Sensible (Lights)
<br />0
<br />0 0
<br />0
<br />-
<br />RA Sensible (Lights)
<br />0
<br />0 0
<br />0
<br />-
<br />Engineering Checks
<br />Engineering Checks
<br />Cooling tons
<br />3.58
<br />Input Ventilation cfm
<br />119
<br />Heating Mbh
<br />-11.60
<br />Input Ventilation cfm
<br />119
<br />Cooling cfm
<br />1,801
<br />Calculated Ventilation
<br />cfm
<br />119
<br />Heating cfm
<br />1,801
<br />Calculated Ventilation
<br />cfm
<br />119
<br />Cooling ACH
<br />17.36
<br />Calculated Ventilation
<br />ACH
<br />1.15
<br />Heating ACH
<br />17.36
<br />Calculated Ventilation
<br />ACH
<br />1.15
<br />Sec Fan cfm
<br />0
<br />Number of People
<br />16.31
<br />Sec Fan cfm
<br />0
<br />Number of People
<br />16.31
<br />ft2/ton
<br />133.03
<br />People per 1000 ft2
<br />34
<br />ft2/Mbh
<br />-41.02
<br />People per 1000 ft2
<br />34
<br />cfm/ton
<br />503.47
<br />Conditioned ft2
<br />475.8
<br />cfm/Mbh-155.29
<br />Conditioned ft2
<br />475.8
<br />Btu/h-ft2
<br />90.21
<br />Volume (ft3)
<br />6,224.6
<br />Btu/h-ft2
<br />-24.38
<br />Volume (ft3)
<br />6,224.6
<br />Alternative: Primary Calculated at: Feb 28, 2024 - 12:09 PM
<br />File EDWARD JONES, EVERETTE, WA.mdf TRACE 3D Plus 5.20.117
<br />name:
<br />
|