City of Everett, WA IMEG #24000280.11 <br />August 21, 2024 Page 3 of 4 <br />IMEG Response: Dampers have been provided at the OA inlet, EA inlet and relief air <br />outlet of the existing energy recovery ventilator. Refer to review drawing M2 and <br />keynote 14 on drawing M2. <br />9. Energy code mechanical requirements sheet M11 <br />IMEG Response: Note that with the addition of the commissioning specifications, this <br />sheet is now sheet M12. <br />a. Page 11 of 25 — It is unclear how setback controls are being specified on sheet M2 as <br />noted. Please clarify. See C403.4.2. <br />IMEG Response: Refer to keynote 4 on drawing M2 and Mechanical Design Conditions <br />on drawing MO. Each fan coil unit is provided with a programmable thermostat and per <br />the Mechanical Design Conditions on drawing MO the setback temperatures are down to <br />550F and up to 85°F. This is in compliance with C403.4.2 and C403.4.2.1. <br />b. Page 11 of 25 — Please provide automatic start and stop, or explain why automatic start <br />and stop are "NA." See C403.4.2.3. <br />IMEG Response: This has been revised to YES on the energy compliance forms. <br />Keynote 4 on drawing M2 has been revised to indicate this requirement as part of the <br />programmable thermostat for the fan coil units. <br />c. Page 12 of 25 — It appears DDC is required per C403.4.11.1. Please revise or note the <br />exception used. <br />IMEG Response: Per Table C403.4.11.1 DDC would be required for Alterations or <br />Additions when air handling systems or fan coil units are being provided and the existing <br />air handling system(s) and fan coil(s) served the same chilled or hot water plant have <br />DDC. The existing systems do not include DDC controls and furthermore there is no <br />chilled or hot water plant. Based on this Table DDC does not appear to be required. <br />d. Page 12 of 25 - Economizers are required per C403.5. Please revise or note exception(s) <br />used. <br />IMEG Response: Exception 9 applies to this project. This project is provided with an <br />existing dedicated outdoor air system that includes energy recovery even though it is not <br />required per C403.7.6. Furthermore, this dedicated outdoor air system with energy <br />recovery does not include mechanical cooling. <br />Page 13 of 25 - It is unclear how plenums and shafts are sealed. Please clarify. See <br />C403.10.1. <br />IMEG Response: Reference on the energy compliance document has been revised to <br />drawing M4. The Ductwork Insulation Schedule has been revised to include outdoor air <br />ductwork shall be insulated with minimum R-7 insulation in accordance with Table <br />C403.10.1.1. Note that the outside air ductwork for this project is inside the conditioned <br />space and conveys less than 2800 CFM. For duct sealing refer to specification section <br />23 3000, 3.2 on drawing M9. <br />Page 13 of 25 — It is unclear how duct pressure are being specified on sheet M2 as <br />noted. Please clarify. See C403.10.2. It is unclear if high pressure duct testing is <br />required. Please clarify, note exceptions as applicable. See C403.10.2.3. <br />IMEG Response: Ductwork pressure classification is indicated in General Note 'C' on <br />drawing M2. General Note 'C' has been revised to indicate the correct code version and <br />reference section. <br />,qk <br />