<br />GRILLES, REGISTERS, & DIFFUSERS SCHEDULE PLUMBING FIXTURE AND EQUIPMENT SCHEDULE
<br />;I,�Ic
<br />'�ry`t�r GROUP
<br />EQUIP TAG TYPE FACE SIZE IN. MOUNTING TYPE DAMPER REQUIRED MATERIAL MANUFACTURER &MODEL... PLAN INFO SPECIFIC NOTES
<br />PLAN FIXTURE ICC/ANSI A117.1 MANUFACTURER SERIES TRIM SERIES SUPPLIES TRAP / DRAIN CW HW / WASTE VENT WATER NOTES / REMARKS
<br />SD-1 LOUVER FACE CEILING DIFFUSER 24" x 24" TILE CLG YES STEEL KRUEGER 1400 NECK /CFM --
<br />St. Louis
<br />orth
<br />319 North 4th Street
<br />RG-1 PERFORATED FACE CEILING RETURN GRILLE 24" x 24" TILE CLG SEE NOTES STEEL KRUEGER 6490/6690 NECK /CFM" 1, 2, 3 CODE COMPLIANT # WASTE TEPID CONSUMPTI...
<br />Suite 1000
<br />BFP-1 REDUCED PRESSURE _ FEBCO LF860 / LF860U --- 1/2" -2" INTEGRAL - - SEE -- - - --- 1, W/MANUFACTURER'S MATCHING
<br />St. Louis, Missouri 63102
<br />GENERAL NOTES:
<br />(314) 231-5700
<br />PRIN. BACKFLOW PREVENTOR WILKINS 375 PLANS AIR GAP DRAIN
<br />1. SEE PLANS FOR NECK SIZE
<br />GD-1 GARBAGE _ IN -SINK- BADGERS -- -- -- - INTEGRAL --- --- 1 1/2" -- --- ELECT: 1/2 HP, 115/1v, 6.3 FLA
<br />"'
<br />2. ALL GRDs REQUIRING DAMPERS SHALL BE EQUIPPED WITH A REMOTE BALANCING DAMPER THAT IS ADJUSTABLE THROUGH THE GRD FACE OR ANOTHER APPROVED
<br />DISPOSAL ERATOR
<br />cEry
<br />LOCATION UNLESS SUPPLIED FROM AN ACCESSIBLE TAKE -OFF WITH LOCKING DAMPER. FACE DAMPERS SUCH AS INTEGRAL OBDs ARE NOT ACCEPTABLE.
<br />T. Be Determined
<br />OB-1 OUTLET BOX _ SIOUX CHIEF 696-# --- --- INTEGRAL P-TRAP - 112" 1/2" 2" 11/2" --- 3,4,5
<br />3. VERIFY GIRD FINISH AND CLG/WALUSILUFLOOR MOUNTING TYPE WITH ARCHITECT FOR EACH APPLICATION PRIOR TO ORDERING.
<br />BEVERAGE DISPENSER ZURN WM2961
<br />4. PROVIDE 4-WAY THROW FOR DIFFUSERS UNLESS OTHERWISE SHOWN ON PLANS.
<br />OB-2 OUTLET BOX _ SIOUX CHIEF 696-# --- --- INTEGRAL - - -- -- 2" 11/2" --- 5
<br />5. PROVIDE MANUFACTURERS ROUND TO RECTANGULAR ADAPTIVE COLLAR FOR DIFFUSERS AND GRILLES AS REQUIRED, MATCH DUCT SIZE AND TYPE
<br />DRAIN ZURN WM2961
<br />6. MATERIAL SHALL BE STEEL UNLESS OTHERWISE INDICATED OR SPECIFIED. MATERIAL SHALL BE SUITABLE FOR INSTALLED ENVIRONMENT. FOR WET
<br />SK-1 SS SINK SINGLE _ GLACIER BAY VT3322TA2PA1 INTEGRAL W/STOPS OFFSET LKAD35 1/2" 1/2" 2" 11/2" 1.5 GPM 2
<br />LOCATIONS SUCH AS LOCKER ROOMS, RESTROOMS, SHOWER ROOMS, KITCHENS, POOL ROOMS, ETC PROVIDE ALUMINUM IN LIEU OF THE STEEL NOTED.
<br />OFF -CENTER DRAIN, CT 9" DEPTH P-TRAP
<br />PRO ENGINEER.
<br />7. WHERE MULTIPLE DIFFUSERS ARE LOCATED IN A SINGLE ROOM; FACE SIZES SHALL BE THE SAME UNLESS NOTED OTHERWISE. SA-1
<br />SHOCK ABSORBER - JOSAM 75000 -- -- -- - - SEE SEE - -- 1
<br />vlMEG
<br />8. AFTER INSTALLATION, ADJUST DIFFUSERS, REGISTERS AND GRILLES TO AIR PATTERNS INDICATED, OR AS DIRECTED, BEFORE STARTING AIR BALANCING.
<br />(WTR-HAMMER ARRESTERS) ZURN Z1700 PLANS PLANS
<br />9. CONTRACTOR SHALL ENSURE ALL NEW GRUS PROVIDED MATCH THOSE WHICH ARE EXISTING IN TERMS OF FINISH AND VISUAL APPEARANCE.
<br />IMEG
<br />WMV-1 THERMAL MIXING - WATTS LFUSG-B -- -- -- - - 3/8" 3/8" - -- -- INSTALL DOWNSTREAM OF
<br />7600 E Orchard Road, Suite 250-S
<br />WHERE CFM IS INDICATED ON PLANS FOR RETURN AND TRANSFERS, BALANCE TO AIRFLOW INDICATED.
<br />Greenwood Village, CO 80111
<br />VALVE, FIXTURE ZURN ZW3870XLT FIXTURE STOPS
<br />:
<br />Phone303.796.6000IMEG
<br />SPECIFIC NOTES:
<br />Project N.: 24000280.07
<br />1. PROVIDE DAMPER FOR A DUCTED RETURN/TRANSFER AIR SYSTEM THAT REQUIRES AIR BALANCE AT RETURN/TRANSFER OPENINGS AS INDICATED BY LEGEND: CH = CHILD HEIGHT, CM = CEILING MOUNTED, CP = CHROME PLATED, CT = COUNTERTOP, FM = FLOOR MOUNTED, FV = FLUSH VALVE, PA = PRESSURE ASSIST, SS = STAINLESS STEEL,
<br />P,mespal seal.
<br />AIRFLOW (CFM.) ON DRAWINGS. TP = PROVIDE TRAP PRIMER (TP-1) ADJACENT TO FIXTURE, WM = WALL MOUNTED (PROVIDE WITH A FLOOR MOUNTED CONCEALED CARRIER), UCT = UNDER COUNTERTOP
<br />W
<br />2. AS IDENTIFIED ON THE PLANS PROVIDE 12"x24' FACE FOR 10"x22" NECKS, PROVIDE 24"x24" FACE FOR 22"x22" NECKS
<br />....,
<br />GENERAL NOTES:
<br />3. PROVIDE BACKPAN WHERE CONNECTED TO DUCT OR SOUND BOOT; WHERE NO DUCT OR SOUND BOOT IS PRESENT PROVIDE PERFORATED PANEL ONLY.
<br />O
<br />1. WHERE FIXTURFIEQUIPMENT MODEL NUMBERS ARE GIVEN THESE ARE FOR REFERENCE ONLY. WRITTEN #WHERE NOTED THE PLUMBING FIXTURE, EQUIPMENT AND ASSOCIATED ACCESSORIES
<br />��.
<br />A'rS7oNq�
<br />SPECIFICATION REQUIREMENTS AND SCHEDULE NOTES HOLD PRESIDENCE. THE MORE STRIGENT SHALL APPLY. SHALL BE ICC/ANSI A117.1 (ADA) COMPLIANT. EXPOSED CW, HW AND W PIPING ALONG WITH
<br />LNG?
<br />DUCTWORK INSULATION (WRAP & LINER) SCHEDULE 2. SEE ARCHITECTURAL DWGS FOR MOUNTING HEIGHTS ON ALL WALL MOUNTED FIXTURES/EQUIPMENT, MIXING VALVE SHALL BE INSULATED. PIPING WITHIN CASEWORK THAT OPENS FOR FIXTURE
<br />9, 1,
<br />ARCHITECTURAL DRAWINGS TAKE PRECEDENCE OVER ANY VALUES WITHIN THIS SCHEDULE. USE IS CONSIDERED EXPOSED.
<br />EXPOSED CONCEALED
<br />SYSTEM LOCATION SERVICE MINIMUM R-VALUE SPECIFIC NOTES 3. THE MINIMUM WASTEIVENT PIPE SIZE FOR BURIED PIPE SHALL BE 2".
<br />NOTE1 RECTANGULAR ROUND/OVAL RECTANGULAR ROUND/OVAL
<br />4. ALL ACCESIBLE FIXTURES SHALL COMPLY WITH ICC/ANSI A117.1 (ADA), REFERENCE ARCH DWGS FOR SPECIFIC LOCATIONS. SEE NOTE #
<br />MAIN 1-1/2" LINER 1-1/2" LINER 1-1/2" LINER 1-1/2" LINER R-6
<br />5. ALL FIXTURES AND EQUIPMENT SHALL BE INSTALLED PER THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.
<br />SUPPLYAIR INDOOR MAINTOTERMINAL 1-1/2"LINER -- 1-1/2"LINER 2" WRAP R-6
<br />TERMINALTO GRD 1-1/2" LINER -- 1-1/2" LINER 2" WRAP R-6 SPECIFIC NOTES:
<br />P,y.arm..
<br />MAIN 1" LINER 1" LINER 1"LINER 1" LINER R-6 1. EQUIPMENT AND/OR ISOLATION VALVE SHALL BE CONCEALED (WITHIN ADJACENT WALL OR WITHIN CASEWORK). WHERE LOCATED IN WALL/CEILING COORDINATE FINAL DEVICE AND ACCESS DOOR LOCATION WITH ARCHITECT.
<br />5 RETURN AIR INDOOR
<br />_ 2. PROVIDE WITH ASSE 1070 RATED THERMAL MIXING VALVE (WMV-1) LOCATED DOWNSTREM OF FIXTURE STOPS UNLESS SERVED FROM AN ASSE 1070 RATED GROUP -FIXTURE THERMAL MIXING VALVE.
<br />�p
<br />0
<br />MAIN 2" WRAP 2" WRAP 2"WRAP 2" WRAP R-7 3. PROVIDE SHOCK ARRESTOR(S) ON HW, CW AND TEPID SUPPLIES.
<br />rn
<br />OUTSIDE AIR -TEMPERED INDOOR
<br />Q
<br />BRANCH 2" WRAP 2" WRAP 2" WRAP 2" WRAP R-7 4. PROVIDE AN ASSE 1022 BEVERAGE DISPENSING BACKFLOW PREVENTOR (BFP-1) FOR EACH BEVERAGE DISPENSER (COFFEE, SODA, ETC..) OR ICE MACHINE PRIOR TO CONNECTION/OUTLET BOX.
<br />3:
<br />5. PROVIDE FIRE RATED BOX WHERE OUTLET BOX IS LOCATED IN A RATED WALL.
<br />d
<br />a�
<br />GENERAL NOTES:
<br />5
<br />Lj
<br />1) MINIMUM R-VALUE BASED IkVSEC REQUIREMENTS-
<br />2)
<br />2) DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. LINER, WHERE USED, WILL NEED TO BE FACTORED INTO THE DUCT SIZE. VRF FAN UNIT SCHEDULE
<br />COIL
<br />Y /1 L lJ J fl lJ L
<br />3) THE INSULATION THICKNESS GIVEN MEETS OR EXCEEDS THE REQUIRED R-VALUE FOR THE BASIS OF DESIGN (JOHNS MANVILLE). INSTALLED PRODUCT SHALL
<br />E.S.P CLG CAP HTG CAPACITIES MOTOR DATA OP UNIT
<br />MEET OR EXCEED THE LISTED R-VALUE; INSULATION THICKNESS AND CORRESPONDING DUCT SIZE (FOR LINER) SHALL BE INCREASED FOR ALTERNATES THAT
<br />FCUTAG CONDENSINGUNIT AREA(S)SERVED OSA IN. W.C. TOTAL SENS CAP CLG EAT HTG EAT W7 MANUFACTURER & MODEL # SIZE NOTESCONTROLS
<br />CANNOT MEET THIS THICKNESS TO PERFORMANCE CONDITION. V-PH MCA MOCP STRTR
<br />Co
<br />CFM CFM ALT. MBH MBH MBH DB WB DB LBS TONS
<br />4) R-VALUES FOR WRAP SHALL BE SHOWN USING THEIR INSTALLED CONDITION RATING AS NOTED ON THE MANUFACTURER'S SPECIFICATION SHEET.
<br />^ ` /'�/'�
<br />FCU-1 (E)COLA BREAK, SMALL CONFERENCE ROOMS 1800 110 0.5 40.7 38.9 16.2 75A 61.2 67.3 2081230-1 7.2 15 INT 165 CARRIER40VMV054A-3 41/2 ALL T-STAT
<br />W w
<br />5) JACKET (PVC OR METAL) SHALL BE INSTALLED AS REQUIRED BY THE SPECIFICATIONS.
<br />FCU-2 (E) ODU-1 BRANCH SUPPORT, OFFICES, EQUIP/SUPPLY 1070 155 0.5 22.8 20.3 14.4 75.9 61.4 63.5 208/230-1 5.0 15 INT 130 CARRIER 40VMM030A--3 21/2 ALL T-STAT
<br />6) FLEXIBLE DUCT SHALL BE AS NOTED IN THE "AIR DUCT ACCESSORIES" SPECIFICATION.
<br />FCU-3 (E)ODU-1 WELCOME, MEDIUM CONFERENCE 1070 95 0.5 21.4 19.9 13.1 75.5 61.2 66.0 208/230-1 5.0 15 INT 130 CARRIER 40VMM03OA-3 21/2 ALL T-STAT
<br />7) DUCT WRAP IS ALLOWED TO BE BLANKET OR BOARD; CONTRACTOR OPTION.
<br />O
<br />FCU-4 (E)ODU-1 LARGE CONFERENCE 430 80 0.5 9.0 7.7 6.0 76.1 61.5 61.7 1 208/230-1 3.2 1 15 INT 130 CARRIER 40VMM012A--3 1 ALL T-STAT
<br />8) MULTIPLE LAVERS OF WRAP OR LINER TO ACHIEVE TOTAL R-VALUE ARE ACCEPTABLE IF INSTALLED PER MANUFACTURER'S INSTRUCTIONS.
<br />DEFINITIONS: NOTES: 1. UNIT SHALL BE CONNECTED TO EXISTING MULTIPORT DISTRIBUTION CONTROLLER AS REQUIRED BY THE MANUFACTURER AND CONNECTED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
<br />EXPOSED DUCT: DUCT THAT IS EXPOSED TO VIEW IN OCCUPIED OR UNOCCUPIED SPACES THAT ARE CONDITIONED. 2. COORDINATE WITH LANDLORD AND BUILDING ENGINEER REGARDING PIPING AND DETAILS FOR EXISTING MULTIPORT DISTRIBUTION CONTROLLER.
<br />CONCEALED DUCT: DUCT THAT IS CONCEALED IN CHASES, SHAFTS, CEILING PLENUMS OR OTHER ASSEMBLY WITHIN THE INSULATED BUILDING ENVELOPE. 3. PROVIDE REFRIGERANT PIPING INSTALLED PER THE MANUFACTURES INSTRUCTION AND BY FACTORY CERTIFIED INSTALLER.
<br />w� w
<br />►Vl N
<br />MAIN DUCT: DUCT FROM THE AIR HANDLING UNIT TO FINAL TERMINAL TAKEOFF. 4. PROVIDE WITH INTEGRAL CONDENSATE PUMP AND CONDENSATE OVERFLOW SWITCH. REFER TO PLUMBING DRAWINGS REGARDING CONDENSATE DRAIN ROUTING.
<br />_ o�
<br />m
<br />MAIN TO TERMINAL DUCT: THIS IS A BRANCH DUCT; TYPICALLY THE DUCT FROM THE MAIN TAKEOFF TO THE TERMINAL (VAV BOX OR EQUIVALENT). 5. PROVIDE WITH FACTORY CONTROLS, WALL -MOUNTED WIRED CONTROLLER; COORDINATE WITH TEMPERATURE CONTROLS PROVIDED WITH BASE BUILDING SYSTEMS.
<br />ILL
<br />TERMINAL TO GIRD DUCT: THIS IS A BRANCH DUCT DOWNSTREAM OF THE TERMINAL (VAV BOX, HEAT PUMP, FAN COIL OR EQUIVALENT). 6. ALL REQUIRED FIELD WIRING AND PROGRAMMING BY THE MANUFACTURER OR A CERTIFIED INSTALLER, COORDINATE WITH TEMPERATURE CONTROLS CONTRACTOR.
<br />p 7 rn o
<br />OUTSIDE AIR TEMPERED: TEMPERED OUTSIDE AIR IS AIR THAT IS HEATED OR COOLED TO WITHIN 10 DEG F OF THE SPACE/SURROUNDING TEMPERATURE. 7. HEATING CAPACITY LISTED IS MINIMUM REQUIRED. SYSTEM SHALL BE SIZED TO ACCOUNT FOR THE REQUIRED DE -RATE ASSOCIATED WITH ALTITUDE, PIPING LENGTH, AND AN AMBIENT TEMPERATURE
<br />m ' ' t /1/'\
<br />INDOOR: DUCT LOCATIONS WITHIN THE INSULATED BUILDING ENVELOPE. OF 20 DEGREES F (WINTER) AND 90 DEGREES F (SUMMER).
<br />W W
<br />2
<br />8. UNIT SHALL BE PROVIDED WITH SINGLE POINT POWER CONNECTION INCLUDING CONTROLS, FAN, AND INTEGRAL CONDENSATE PUMP.
<br />��
<br />o me�m,a uems mown
<br />Lj
<br />a m zrb ongm
<br />9. CONTACT JEFF MILLER AT LOHMILLER COMPANY (303) 598-8413 FOR ADDITIONAL PRODUCT INFORMATION AND ORDERING.
<br />PLUMBING INSULATION SCHEDULEeTy�r,
<br />M1paB,d�.ipeorm
<br />w
<br />PIPE SIZES
<br />w
<br />SYSTEM INSULATION TYPE FLUID TEMPERATURE RANGE SPECIFIC NOTES
<br />DOMESTIC WATER HEATER SCHEDULE
<br />= arMrtlHaivaeExlal
<br />w
<br />I
<br />DOMESTIC COLD WATER FLEXIBLE ELASTOMERIC OR GLASS FIBER PREFORMED PIPE INSULATION -- 1/2" 1/2" 1
<br />%pecifcM1ie pro ed only.
<br />Ioe a, Popi•a o- r.wod-d. mw .1
<br />r�r omarvxm".a or wianrnrrow me
<br />141 TO 200 DEG F 1-1/2" 1-1/2" HEATING CAPACITY ELEC MOTOR DATA MANUFACTURER &MODEL
<br />"""'a"CO..M-M r"h-
<br />°J
<br />DOMESTIC HOT WATER GLASS FIBER OR MINERAL FIBER PREFORMED PIPE INSULATION ITEM SERVICE TANK CAP. [GAL] OPERATING WEIGHT [LBS] NO. NOTES CONTROLS
<br />g
<br />< 140 DEG F 1" 1" ELEC OUTPUT [kW] RECOVERY [GPH] TEMP RISE [°F] FLA V-PHN,
<br />Descriptbn Data
<br />1 Revision 1 Date 1
<br />NI
<br />CONDENSATE AND EQUIPMENT DRAIN WATER FLEXIBLE ELASTOMERIC OR GLASS FIBER PREFORMED PIPE INSULATION <60 DEG F 112" 1" EWH-1 BREAK 108 20 2 8 100 9.6 208-7 225 AO SMITH DEL-20 1, 2 INTEGRAL
<br />2
<br />FOR CONSTRUCTION
<br />07/11/2024
<br />a
<br />3
<br />MECH PERMIT
<br />07/24/2024
<br />w
<br />5
<br />MECH REVIEW
<br />011/21/2024
<br />GENERAL NOTES: GENERAL NOTES (APPLY TO ALL PRODUCT):
<br />1) FOR PIPING EXPOSED TO THE OUTSIDE AMBIENT CONDITIONS OR PIPING PROVIDED WITH HEAT TRACE, INCREASE THICKNESS OF INSULATION BY 1/2". 1) CONTROLS: INTEGRAL =INTERNAL CONTROLS PROVIDED WITH UNIT, DDC =DIRECT DIGITAL CONTROLS BY DIV 23, OTHER SEE NOTES
<br />a-
<br />2) FOR PIPING EXPOSED TO THE OUTSIDE AMBIENT CONDITIONS PROVIDE PROTECTIVE JACKET (SEE SPECIFICATIONS). 2) INSTALL WATER HEATER AND PIPING PER SELECTED MANUFACTURER'S WRITTTEN INSTRUCTIONS
<br />r
<br />MECHANICAL AN D
<br />3) ALL INSULATION EXPOSED TO UV CONDITIONS SHALL BE PROTECTED IN ACCORDANCE WITH THE MANUFACTURERS WRITTEN INSTRUCTIONS. SPECIFIC NOTES (APPLY WHERE NOTED):
<br />PLUMBING
<br />3
<br />4) MINIMUM THERMAL CONDUCTIVITY "k" VALUE FOR FLEXIBLE ELASTOMERIC SHALL BE 0.27 AT 75 DEG. F
<br />SCHEDULES
<br />1) ALL ELEMENTS RUN SIMULTANEOUSLY. kW AND AMPERAGE LISTED ARE FOR ALL ELEMENTS BEING ON.
<br />vxrwxaPe.. sLxxare«.
<br />wi
<br />5) MINIMUM THERMAL CONDUCTIVITY "k" VALUE FOR GLASS FIBER SHALL BE 0.23 AT 75 DEG. F
<br />2) PROVIDE SINGLE POINT ELECTRICAL POWER CONNECTION WITH FACTORY INSTALLED FUSED DISCONNECT FOR HEATING ELEMENTS AND CONTROLS.
<br />2024906.011
<br />o
<br />0
<br />T
<br />SPECIFIC NOTES:
<br />1) PROVIDE PIPE INSULATION WICKING SYSTEM ON ALL EXISTING SYTEMS THAT ARE OPERATIONAL DURING INSTALLATION.
<br />oa." sr
<br />MSK
<br />a
<br />i:a,. on.:
<br />M4
<br />MARCH 27, 2024
<br />
|