Laserfiche WebLink
� rt e st <br /> Roof Top Unit <br /> PROJECT: Kaiser Permanente EMCE DATE: 2/15/2024 <br /> LOCATION: Everett,WA CONTACT: Shane Moore <br /> PROJECT#: 230035 AUTHOR: Adam Hoskins <br /> System/Unit Area Served Outlet Size LxW Design <br /> Type D CFIVI Reading Reading <br /> Inlet-100 CT Hallway RG 6 RD 50 50 45 90 <br /> Inlet-101 MRI Storage RG 10 RD 300 280 275 92 <br /> Inlet-102 ESOR MRI RG 10 RD 200 200 190 95 <br /> Inlet-103 ESOR MRI RG 8 RD 335 230 230 69 <br /> Inlet-104 MRI Entry RG 6 RD 100 80 80 80 <br /> Inlet-105 MRI Entry RG 6 RD 100 70 70 70 <br /> Inlet-106 MRI Entry RG 8 RD 110 80 90 82 <br /> Inlet-107 MRI Hallway RG 6 RD 85 70 70 82 <br /> Inlet-108 1627 Imaging Office RG 8 RD 140 130 135 96 <br /> Inlet-109 1628 Office RG 6 RD 75 45 70 93 <br /> Inlet-110 1627 Imaging Office RG 12 RD 305 350 420 1 138 <br /> Inlet-111 1629 Office RG 6 RD 65 60 85 131 <br /> Inlet-1 12 Hallway RG 8 RD 85 80 80 94 <br /> Inlet-113 Clean Linen Storage RG 6 RD 50 50 55 110 <br /> Inlet-1 14 1615 Conference Room RG 6 RD 115 165 165 143 <br /> Inlet-115 Hallway RG 6 RD 100 90 100 100 <br /> Inlet-116 1501 Staff Lounge RG 12 RD 405 375 360 89 <br /> Inlet-117 Hallway RG 8 RD 100 90 100 100 <br /> Inlet-118 1606 Fluoroscopy RG 8 RD 120 125 175 146 <br /> Inlet-119 1607 Bone Density RG 8 RD 285 205 190 67 <br /> Inlet-120 1608 Scan RG 12 RD 335 290 275 82 <br /> Inlet-121 1608 Scan RG 10 RD 330 300 285 1 86 <br /> Inlet-122 Hallway RG 10 RD 200 185 185 93 <br /> Inlet-123 1217 Supply Storage RG 8 RD 185 165 145 78 <br /> Inlet-124 1603 Office RG 6 RD 90 90 90 100 <br /> Inlet-125 1602 Office RG 6 RD 90 90 90 100 <br /> Inlet-126 Hallway RG 8 RD 200 180 180 90 <br /> Inlet-127 1811 Staff Lounge RG 14 RD 420 390 385 1 92 <br /> Inlet-128 1811 Staff Lounge RG 14 RD 425 390 385 91 <br /> Inlet-129 1814 Office RG 6 RD 50 40 60 120 <br /> Inlet-130 1813 Office RG 6 RD 50 50 60 120 <br /> Inlet-131 1812 Office RG 6 RD 50 45 65 130 <br /> Inlet-132 1811 Kitchenette RG 12 RD 330 300 305 92 <br /> Inlet-133 1811 Kitchenette RG 12 RD 330 285 1 310 94 <br /> Inlet-134 Electrical Room RG 12 x 12 480 430 440 92 <br /> Inlet-135 Exam Room 3 RG 8 RD 125 110 110 88 <br /> Inlet-136 1804 Soiled Utility RG 10 RD 260 240 245 94 <br /> Inlet-137 Basement Plenum RG 8 RD 750 750 100 <br /> Inlet-138 Basement Plenum RG 8 RD 755 750 99 <br /> Inlet-139 Exam Room 4 RG 8 RD 130 100 1 125 96 <br /> Inlet-140 1306 Office RG 6 RD 75 90 90 120 <br /> Inlet-141 1217 RG 10 RD 185 435 435 235 <br /> Inlet-142 1847 Consult RG 8 RD 90 85 85 94 <br /> Inlet-143 1608 Control RG 8 RD 180 165 165 1 92 <br /> Airtest Co. LLC <br /> Preliminary TAB Report <br />