Laserfiche WebLink
,A. i <br /> Roof Top Unit <br /> PROJECT: Kaiser Permanente EMCE DATE: 2/15/2024 <br /> LOCATION: Everett,WA CONTACT: Shane Moore <br /> PROJECT#: 230035 AUTHOR: Adam Hoskins <br /> SYSTEM/UNIT: RTU-01/CAV-1-0-02 Tested By: Tyler Balazic <br /> Date: 2/8/2024 <br /> Unit Data <br /> Manufacturer Titus <br /> Model Number DESV <br /> Controls System Siemens <br /> VAV Type Shut-Off <br /> Box Inlet Size 8 RD <br /> RTU-01/CAV-1-0-02 Autoflow Valve Summary <br /> .- <br /> 7AV-1-0-072* Griswold MCK21RIR1 FH M0.752-32 0.50 <br /> .11111111111116 <br /> Log: RTU-01/CAV-1-0-02/CAV-1-0-02 2/8/2024 Tyler Balazic Low flow <br /> SYSTEM/UNIT: RTU-01/VAV-1-1-01 SWD w Tested By: Hayden Lindsay <br /> Date: 1/31/2024 <br /> Unit .. . Air Test Data Titus Design Primary Max CFM 480 CFM <br /> Model Number DESV Design Primary Min.CFM 150 CFM <br /> Controls System Siemens <br /> VAV Type Shut-Off <br /> Box Inlet Size 8 RD <br /> RTU-01/VAV-1-1-01 SWD w Supply Outlet Summary <br /> DesignSystem/Unit Outlet <br /> Type L CFM ­Rgadj= Reading <br /> Outlet-01 SWD 480 <br /> RTU-01/VAV-1-1-01 SWD w Autoflow Valve Summary <br /> System/Unit Area Served MFG Valve .- Range Actual DP <br /> Rating (PSI) (PSI) <br /> L_ GPM <br /> Autoflow Valve- Heating Water Griswold MCK2IRIR1 FH 0.80 1.00 2-32 3.00 <br /> 01 <br /> Airtest Co. LLC <br /> Preliminary TAB Report <br />