Mr. Jeff Hencz <br />Snohomish Count Property Management <br />Plan Check Number: B2206-040, First Building Review <br />July 12, 2022 <br />have both latches and closers. One or both doors should comply with the maneuvering <br />clearances of ICC A117.1-09 Section 404.2.3. See IBC Sections 1009 and 1101.2. <br />11. The new west ramp in Corridor 3510 is required to have a minimum 5-foot landing at the <br />bottom per ICC A117.1-09 Section 405.7. An existing partial wall conflicts with the ramp <br />length. See IBC Section 1101.2. In addition, please note the following: <br />a. The end of the ramp results in potential conflicts with the existing door in the north wall and <br />the required handrail. <br />b. ICC A117.1-09 Section 405.7.5 prohibits the required landing from overlapping with the <br />doorway, though the landing and doorway maneuvering clearance are allowed to overlap. <br />It is noted that the door doesn't swing into the landing area, and that the conflicting <br />doorway is located at the bottom landing. This condition should be reviewed and revised as <br />needed. <br />12. Elevations for Bathrooms 3508 and 3509 are provided on Sheet IF-428. See IBC Section <br />1102.1, and references below to ICC A117.1-09 unless noted otherwise. The following <br />comments should be addressed: <br />a. Show accessible clearances per Sections 603, 604.3, and 606.2. <br />b. Show centerline dimension for the water closet measured from the side wall per Section <br />604.2. <br />c. Show centerline dimension for the sink measured from the side wall per IBC Section <br />107.2.1. <br />d. Provide dimensions for the grab bars per Sections 604.5.1 and 604.5.2, and Figures 604.5.1 <br />and 604.5.2. <br />e. Provide water closet seat height dimension per Section 604.4. <br />f. Provide a vertical grab bar on the sidewall per Figure 604.5.1. <br />g. Provide sink pipe insulation per Section 606.6. <br />h. Locate the water closet flush control on the open side per Section 604.6. <br />i. Provides signage per IBC Section 1111.1. <br />13. Vestibule 3511 in Plan 2/IF-423 includes two doors in series. See IBC Section 1101.2, and <br />references to ICC A117.1-09 in the following comments: <br />a. The vestibule should specify a minimum 48-inch clearance per Section 404.2.5. <br />b. The doors should comply with the maneuvering clearances per Section 404.2.3. <br />Miscellaneous: <br />14. The water closet in Room 3513 in Plan 2/IR-423 does not appear to comply with the clearance <br />requirements of UPC 402.5. The clearance should be minimum 15 inches to each side. The <br />unobstructed clearance in front of the water closet should be 24 inches deep for the 15-inch <br />clearance to each side. <br />(S 3200 Cedar Street <br />Everett, WA 98201 <br />© 425.257.8810 O <br />425.257.8857 fax <br />everetteps@everettwa.gov <br />eve rettwa.gov/perm its <br />Page 3 of 4 <br />