Lighting, Motor and Electrical Requirements List, pg 5 of 13 <br /> 2021 WSEC Requirements for Commercial Buildings including Group R2,R3&R4 over 3 stories&all R1-- Administered by©2024 NEEA,All rights reserved <br /> The following information is necessary to check a permit application for compliance with the lighting systems,motors and electrical system requirements in the <br /> Washington State Energy Code,Commercial Provisions. <br /> For questions about this report,contact WSEC Commercial Technical Support at 360-539-5300 or via email at com.techsupport@waenergycodes.com <br /> NA C405.8.3 High end trim Where high end trim is required,luminaires <br /> shall be initially configured to limit maximum <br /> lumen output or lighting power to 85%or to <br /> the target design lighting power. <br /> INTERIOR LIGHTING CONTROLS-ADDITIONAL ENERGY EFFICIENCY MEASURE <br /> C406.2.4.2 Enhanced digital To comply with the enhanced interior lightins <br /> interior lighting controls measure.provide calculations that <br /> controls demonstrate that lighting in>_50:4-of the <br /> project floor area is provided with LLLC <br /> (C405.2.8.1)or NLC(C405.2.8.2)controls <br /> with high end trim tC405.2 8.3) <br /> Where LLLC is provided,indicate on plans <br /> that each LLLC controlled luminaire is <br /> configured with integral sensors;where NLC <br /> is provided.indicate on plans that each NLC <br /> controlled luminaire is configured to he <br /> independently addressable;provide sequence <br /> C406.2.4.1 Enhanced lighting In Group R-2 occupancies,indicate on plans a <br /> controls in Group R-2 master control at the main entrance to each <br /> dwelling or sleeping unit that switches off all <br /> lights and switched receptacles(may be two <br /> controls,one for lights and the other for <br /> receptacles);indicate on plan <br /> INTERIOR LIGHTING CONTROLS-LIGHTING LOAD MANAGEMENT MEASURE <br /> NA C406.3.1 Interior lighting DDC To comply with the interior lighting load <br /> controls&real-time management measure,indicate automatic <br /> demand response lighting controls are connected to a central <br /> DDC system capable of activation by an <br /> external utility signal;where utility real-time <br /> demand or pricing program exists,indicat <br /> NA C406.3.1 Interior lighting Indicate lighting controls are configured to <br /> power reduction gradually reduce by continuous dimming the <br /> controls interior general area lighting power by?20% <br /> in response to a peak demand signal;calculate <br /> the percentage of total building floor area <br /> served by load management ligh <br /> NA C406.3.1 Warehouse&retail For warehouse&retail storage areas,indicate <br /> storage interior method of interior general area lighting power <br /> lighting power reduction(continuous dimming by?20%; <br /> reduction controls switching off?25%of lighting power). <br /> EXTERIOR LIGHTING CONTROLS <br /> C405.2.9 Exterior lighting For all exterior lighting,indicate on plans <br /> C405 2.9.I controls automatic controls teither daylight sensing or <br /> C405.19 astronomic time clock)configured to turn <br /> lighting off when daylight is present:or <br /> indicate exception applied. <br /> For exterior building facade&landscape <br /> lighting,indicate that controls are configured <br /> to turn this lighting off w hen daylight is <br /> present for a minimum of 6 hours per night, <br /> or from I hour after closing to 1 hour before <br /> opening per the occupancy schedul <br /> Page-6fF9 <br /> l v `lo <br />