Laserfiche WebLink
Distribution Piping Requirements —6.0 Gallon Manifolded IN-LINE BURST DISC ASSEMBLY(MANIFOLDED <br /> System (Continued) SYSTEMS ONLY) <br /> This configuration consists of two 3 gallon tanks. Both tanks are The in-line burst disc assembly is required to eliminate the <br /> connected to a common manifold tee and are pressurized from a siphoning of the agent up the pipe during extreme temperature <br /> single double tank (Part No. 73022) nitrogen cartridge in the regu- variations. In addition to eliminating the siphoning effect, the <br /> ► lated release assembly. See Figure 115. Note: A tank mounting common in-line burst disc assembly eliminates the possibility <br /> bracket can be utilized instead of the tank/enclosure assembly. of one or more individual discs located in the tank adaptor from <br /> ►See Figure 117. failing to burst. The assembly consists of a stainless steel body <br /> which houses the burst disc. When utilizing this assembly in a <br /> SUPPLY SUPPLY SUPPLY BRANCH manifolded system, it is necessary to modify(remove)the burst <br /> 3/8 IN. IN. ors e system.y disc located in all of the R-102 tank adaptors in the stem.The <br /> � <br /> USE HOSE/ SEE 1 1 in-line burst disc assembly is to be mounted as close to the tank <br /> GROMMET ~NOTE outlet as possible. Afters stem discharge, the assembly must <br /> PACKAGE NO.1 p y g y <br /> (PART NO. 3/8 IN BRANCH be disassembled and a new burst disc installed. <br /> 418511) <br /> IN-LINE BURST DISC Part No. Description <br /> ASSEMBLY—SEE NOTE NO.4 416970 In-Line Burst Disc Assembly <br /> 417911 Burst Disc(Pack of 10) <br /> REMOVE 1.54IN. <br /> `I BURST DISC— (39 mm) <br /> E SEE NOTE NO.3 <br /> I I I <br /> 3.0 3.0 <br /> GALLON GALLON <br /> TANK TANK <br /> I DOUBLE TANK <br /> j NITROGEN — i— — — — — —i--- <br /> ! CARTRIDGE OR <br /> i <br /> i <br /> (LT-A-101-30 <br /> CARTRIDGE— <br /> 3.0 GALLON REGULATED RELEASE 008127 REGULATED <br /> ACTUATOR ONLY) <br /> ASSEMBLY OR 3.0 GALLON REGULATED <br /> ACTUATOR ASSEMBLY <br /> TANK/ENCLOSURE RED SIDE OF BURST <br /> ASSEMBLY DISC TO BE TOWARDS <br /> ADAPTOR(PART NO.417707) <br /> NOTE 1: THE PIPE CONNECTION FROM TANK CENTER TO TANK FIGURE 3-34 <br /> CENTER CANNOT EXCEED 8-1/2 IN.(21.5 cm).ALSO,OEM <br /> RELEASE/BRACKET ASSEMBLY CAN BE UTILIZED WHEN 008383 <br /> MANIFOLDING 3.0 GALLON TANK. <br /> NOTE 2: ONLY 3 GALLON TANKS CAN BE MANIFOLDED. <br /> NOTE 3: THE BURST DISC THAT IS PART OF THE TANK <br /> ADAPTORBURST DISC ASSEMBLY MUST BE REMOVED <br /> AND MODIFIED.SEPARATE THE ALUMINUM DISC PYE <br /> MATERIAL FROM THE PLASTIC GASKET.DISCARD THE <br /> ALUMINUM DISC MATERIAL AND REINSTALL THE BARKER <br /> PLASTIC GASKET BACK INTO THE TANK <br /> ADAPTOR/BURST DISC ASSEMBLY. 13 11.1 1 Goff*r.FGr 191; <br /> NOTE 4: THE IN-LINE BURST DISC ASSEMBLY, PART NO.416790, LUNA MEXICAN RESTAURANT <br /> IS TO BE MOUNTED AS CLOSE TO THE TANK OUTLET AS <br /> POSSIBLE.AF-rER SYSTEM DISCHARGE,THE ASSEMBLY 6600 EVERGREEN WAY <br /> MUST BE DISASSEMBLED AND A NEW BURST DISC <br /> INSTALLED. EVERETT, WA 98203 <br /> ' FIGURE 115 735 E. FAIRHAVEN AVE. SIZE DWG No DWG REV <br /> BURLINGTON, WA 98233 KITCHEN FIRE SYSTEM 1 <br /> (360) 755-5444 SCALE N/A 11/17/2023 SHEET 3 OF 11 <br />