Laserfiche WebLink
2. Access - O.K. as shown on the site plan reviewed. <br />3. A Knox Box is required. Order box #3270 go to www.everettwa.gov/fire to order. <br />4. Knox fire department connection caps are required for all OUTSIDE FDC and standpipe connection <br />points. Order caps #3041 go to www.everettwa.gov/fire to order. <br />5. Fire lanes shall be provided as required in Everett Municipal Code 46.44. Fire lanes shall be identified <br />by red curbs with white stenciling stating "NO PARKING - FIRE LANE" and vertical signs stating "NO <br />PARKING — FIRE LANE — TOW AWAY ZONE — EMC 46.28.130". Location shall be approved by the <br />Fire Code Official using field review per Fire Marshal's Office. <br />6. Premises shall be clearly identified by the correct address at the street entry. Buildings shall be clearly <br />identified so as to be visible and legible from the access road. Individual apartments and suites, where <br />applicable, shall be clearly and legibly identified from the access road. See EMC 16.03, Section 505.1.1 <br />(Address Posting Policy). Address at entry and 12" numbers on building. <br />7. Fire Hydrants - Locations as planned are acceptable. <br />8. Fire flow for this project is 1650 gpm. <br />9. A portable fire extinguisher with a minimum U.L. rating of 2-A:10-B:C shall be provided within 75 feet of <br />travel on all floors of each building during construction and prior to occupancy. <br />10. An approved automatic fire detection system shall be provided as required by City Ordinance No. 3021- <br />07, Chapter 16.76, of the Everett Municipal Code. <br />Plans for such system shall be submitted to the Fire Code Official for review and approval prior to <br />installation. Submittal shall include cut sheets of all equipment intended for use. Appropriate trip tests, <br />witnessed by a Fire Department Inspector, shall be performed, along with a certificate of completion, <br />prior to final acceptance of the system. <br />Fire alarm systems shall be installed according to NFPA Chapter 72, 2010 Edition. Installation of fire <br />alarm components, including basic wiring, may not commence before plans are approved by the Fire <br />Department Plan Reviewer. Fire alarm drawings must be professionally rendered, in sufficient detail, <br />and must be internally consistent. Riser diagrams must match installation plans and load calculations. <br />Components must be listed and approved for use together. Changes to plans must include new <br />drawings and calculations and must be approved by the Fire Department Plan Reviewer prior to <br />installation. Fire alarm installation is subject to field inspection by a Fire Department Inspector. An <br />approved set of plans and the Engineering & Public Services Department electrical permit must be <br />present for any installation inspection. <br />Fire alarm systems shall be installed under permit of the City of Everett Engineering & Public Services <br />Department. Electrical inspections and approval are required prior to calling for acceptance tests. Call <br />(425) 257-8810 for permit information. The absence of monitoring for the alarm system will because <br />for postponing Fire Department inspection and testing and shall result in denial of occupancy. <br />A copy of NFPA 72 Record of Completion form must be filled out prior to final occupancy (NFPA 72, <br />2010 Edition, Chapter 10, page 114). <br />Call for design requirements per Authority Having Jurisdiction <br />�/. <br />