Laserfiche WebLink
indoors in an ordinary (non-hazardous) location, and has been <br /> evaluated for use in this location only. <br /> 7.3.2 Grounding <br /> Exposed non-current carrying parts of the equipment were verified <br /> to be effectively grounded in accordance with the applicable <br /> provisions of NEC', Article 250. <br /> 7.3.3 Guarding of Live Parts <br /> All internal components are enclosed in a grounded, screw closed, <br /> metal enclosure, and are effectively guarded per NEC°, Section <br /> 110.27. <br /> 7.3.4 Overcurrent Protection <br /> Overcurrent protection was provided by a 1 Amp breaker. <br /> Additional overcurrent protection was provided by devices as <br /> shown on the electrical diagrams. <br /> 7.3.5 Wiring <br /> All wiring was found to be UL listed or recognized type MTW/THHN <br /> or equivalent. <br /> 7.3.6 Equipment Discrepancies <br /> No discrepancies were observed during the evaluation of the <br /> equipment listed in Section 5.0. <br /> 7.4 Two Relocated Slide Out Panels <br /> 7.4.1 System Description <br /> The equipment inspected consists of Two Relocated Slide Out <br /> Panels manufactured by El. The equipment is rated at 480VAC, 3 <br /> Phase, 60HZ, 33 Amps, 10KA and is used as part of cell 6 and 7 <br /> controls and was previously labeled but the panels were <br /> disconnected and reconnected. The equipment is installed indoors <br /> in an ordinary (non-hazardous) location, and has been evaluated <br /> for use in this location only. <br /> Reference No.: 1108546 Page 8 <br />