Laserfiche WebLink
GENERAL NOTE <br />THE FOLLOWING NOTES APPLY UNLESS NOTED OTHERWISE-ASTM'S NOTED ARE TO BE LATEST EDITION. <br />1. DESCRIPTION <br />Building Name & Site Location - BAKER VIEW LOGISTICS CENTER, EVERETT, WA. <br />2. DESIGN CODE AND STANDARDS <br />Applicable Code (Edition/Name) - 2018 International Building Code (IBC) <br />Other documents referenced by these notes shall be the specific edition referenced by the building code <br />specified above, or if not specified, shall be the latest edition. <br />Code supplement & Date -ASCE 7-16 <br />3. DESIGN LOADS <br />a. Roof Live Load See snow load <br />II. Future Mezzanine 50 psf (reducible per code) + 15 psf (unreducible) <br />Live Load <br />b. Snow Load Basic roof snow load - Pf = 25 psf <br />Thermal factor- Ct - 1.0 <br />Snow exposure factor - Ce = 1.0 <br />b. Seismic I Risk Category II Basic Seismic Farce Resisting System is Special Reinforced Concrete <br />Shear walls in E-W and N-S directions (R=5) and steel ordinary braced frames (R=3.25) in <br />E-W direction. <br />S. = 1.373, S, = 0.488, le =1.0. Site Class "C" and <br />SOs = 1.0, So, = 0.489. Cs = 0.2 NS and 0.308 E-W. <br />Seismic Design Category = "D" <br />Mach. & Refrigeration unit loads will be picked up at the point of the units <br />and transferred into the lateral system. <br />Sprinkler lines will be braced to top of girders or top chord of steel truss, <br />by the sprinkler contractor. <br />c. Wind Load Risk Category II <br />9 ry <br />Basic winds speed 3 sec. u - - <br />e gust) V -110m h V -85m h <br />P ( 9) u�T P o P as <br />Exposure B <br />Kzt= 1.0 Ke= 1.0 <br />Kd=0.85 (Per ASCE 7, Table 26.6-1) <br />Internal pressure coefficient GCpi -+ 0.18 <br />d. Dead loads Weight of structure. <br />e. Special Loads The following special loads are to be considered: <br />Mechanical equipment on roof. <br />Sprinkler lines, canopy & other reactions as noted on structural <br />drawings. <br />f. Load Combinations All Code required load combinations are to be used in the building design. <br />OSHA STANDARDS <br />THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PROVISIONS OF THE CURRENT OSHA <br />STANDARDS. THE GENERAL CONTRACTOR SHALL REVIEW THESE STRUCTURAL DRAWINGS FOR ANY <br />NONCOMPLIANCE WITH OSHA STANDARDS, TAKING INTO ACCOUNT THE GENERAL CONTRACTOR'S MEANS <br />AND METHODS. THE GENERAL CONTRACTOR SHALL INFORM ENW OF ANY NONCOMPLIANCE SO THE <br />DRAWINGS MAY BE MODIFIED FOR COMPLIANCE PRIOR TO CONSTRUCTION. THE GENERAL CONTRACTOR IS <br />TOTALLY RESPONSIBLE FOR MEANS AND METHODS AS WELL AS JOBSITE SAFETY ON THIS PROJECT. <br />FOUNDATION <br />THE FOUNDATION WAS DESIGNED WITH AN ALLOWABLE SOIL BEARING CAPACITY OF 2500 PSF IN <br />ACCORDANCE WITH SOILS REPORT #2021-557-2 DATED 10-1-2021 PREPARED BY RILEY GROUP, U.C. <br />PREPARE THE SITE PER SOILS ENGINEER'S RECOMMENDATIONS. .BEAR ALL FOOTINGS AND SLABS ON <br />PROPERLY PREPARED NATIVE SOILS OR ON COMPACTED STRUCTURAL FILL, SEE SOILS REPORT. COMPACT <br />ALL STRUCTURAL FILL AND BACKFILL PER SOILS ENGINEER'S RECOMMENDATIONS. DETERMINE MAXIMUM <br />DENSITY BY ASTM D 1557. EXTEND BOTTOM OF ALL EXTERIOR FOOTINGS 18" MIN. BELOW FINAL FINISHED <br />GRADE. FOOTING STEP LOCATIONS SHOWN ON PLANS ARE APPROXIMATE. CONTRACTOR TO VERIFY AND <br />COORDINATE FOOTING STEPS WITH CIVIL ENGINEER TO FINISH GRADE PLANS. ADD FOOTING STEPS AS <br />REQUIRED. SEE ARCH. AND SOILS REPORT FOR SLAB ON GRADE UNDERLAYMENT. COEFFICIENT OF <br />FRICTION = 0.30. PASSIVE RESISTANCE = 250 PCF. ACTIVE EARTH PRESSURE = 35 PCF. AT -REST PRESSURE _ <br />50 PCF. <br />SLABS ON GRADE <br />THE SLAB ON GRADE FOR THIS PROJECT IS TYPICAL OF THAT IN OTHER BUILDINGS WITH SIMILAR FLOOR <br />LOADINGS AND SOIL CONDITIONS. THE SLAB HAS NOT BEEN DESIGNED FOR ANY SPECIFIC LIVE LOAD <br />(INCLUDING CONSTRUCTION LOADS) AND HAS BEEN DETAILED TO MEET LOCAL INDUSTRY STANDARDS FOR <br />SIMILAR BUILDINGS. <br />REVIEW WITH THE SOILS ENGINEER ANY CONSTRUCTION LOADINGS ON THE SLAB AND SOILS BELOW. TAKE <br />NECESSARY MEASURES TO INSURE THAT THE SLAB AND SOILS BELOW WILL NOT BE EFFECTED OR <br />DAMAGED BY THE CONSTRUCTION LOADING. <br />CONCRETE <br />PROVIDE 28-DAY STRENGTH PER SCHEDULE. SEE ACI 318-14, TABLE 19.3-.2.1 FOR MINIMUM REQUIREMENTS. <br />FOR SPECIAL CONDITIONS ANOTHER CEMENT TYPE MAY BE REQUIRED. - SUBMIT MIXES FOR APPROVAL, <br />ULTIMATE STRENGTH DESIGN METHOD USED. MIXING AND PLACING OF ALL CONCRETE AND SELECTION OF <br />MATERIALS SHALL BE IN ACCORDANCE WITH THE ACI CODE 318. PROPORTIONING OF AGGREGATE TO <br />CEMENT SHALL BE SUCH AS TO PRODUCE A DENSE WORKABLE MIX WITH 4" MAXIMUM SLUMP (UNLESS <br />SUPERPLASTICIZERS AND/OR WATER REDUCING AGENTS ARE USED) WHICH CAN BE PLACED WITHOUT <br />SEGREGATION OR EXCESS FREE SURFACE WATER. FOR ADMIXTURES, SEE SPECIFICATIONS. PROVIDE 314" <br />CHAMFER AT ALL EXPOSED EDGES, UNLESS INDICATED OTHERWISE ON ARCHITECTURAL DRAWINGS. <br />WATER CURING SHALL BE USED. AIR ENTRAIN ALL CONCRETE EXPOSED TO WEATHER PER SCHEDULE. <br />LIMIT WATER TO CEMENT RATIO PER SCHEDULE. ADD NO WATER TO CONCRETE AT SITE. IF INCREASED <br />WORKABILITY IS REQUIRED, CONTRACTOR IS TO SUBMIT A MIX DESIGN THAT WILL ALLOW THE ADDITION OF <br />A FIXED AMOUNT WATER REDUCING AGENT OR A FIXED AMOUNT OF SUPER -PLASTICIZER AT THE CONCRETE <br />PLANT. ACI 306R IS TO BE FOLLOWED FOR COLD WEATHER CONCRETING. ACI 305R IS TO BE FOLLOWED <br />FOR HOT WEATHER CONCRETING. THE TESTING LAB MUST APPROVE THE CONTRACTORS METHOD OF <br />COMPLIANCE AND CERTIFY THEIR APPROVAL WITH EACH CONCRETE TEST CYLINDER THEY CAST. TESTING <br />LAB TO NOTIFY THE ARCHITECT AND ENGINEER IMMEDIATELY OF ANY NONCOMPLIANCE. <br />REINFORCING STEEL <br />USE DEFORMED CONCRETE REINFORCING STEEL CONFORMING WITH ASTM A 615, GRADE 60 (fy=60,000 PSI). <br />LAP CONTINUOUS REINFORCING BARS PER SCHEDULE, 2'-0" MIN. UNLESS NOTED OTHERWISE. PROVIDE <br />CORNER BARS (2'-0" MIN. BEND) FOR ALL HORIZONTAL REINFORCEMENT. DETAIL STEEL IN ACCORDANCE <br />WITH "ACI MANUAL OF STANDARD PRACTICE OF DETAILING REINFORCED CONCRETE STRUCTURES". <br />WELDED WIRE FABRIC (WWF) TO CONFORM WITH ASTM A 185. REINFORCING HOOKS TO COMPLY WITH <br />STANDARD ACI HOOKS EXCEPT STIRRUPS AND TIES SHALL HAVE 135 DEGREE ACI SEISMIC HOOKS. <br />COVER TO REINFORCEMENT: <br />NONPRESTRESSED CAST -IN -PLACE CONCRETE _ (INCHES) <br />CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH..............:................................3 <br />FORMED SURFACES <br />EXPOSED TO EARTH OR WEATHER...............................#6 AND LARGER ............................ 2 <br />#5 AND SMALLER .......................1-t12 <br />NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND <br />SLABS, WALLS. JOISTS ................................................. 14 AND LARGER ............................. 1-1/2 <br />#11 AND SMALLER ...........................3/4 <br />BEAMS, COLUMNS <br />PRIMARY REINFORCEMENT, TIES, STIRRUPS,SPIRALS....................::..................................1-1/2 <br />PRESTRESSED CAST -IN -PLACE CONCRETE (APPLIES TO PRESTRESSED AND NONSTRESSED <br />REINFORCEMENT, DUCTS AND END FITTINGS) <br />CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH......................................................3 <br />FORMED SURFACES <br />EXPOSED TO EARTH OR WEATHER <br />SLABS, WALLS, JOISTS ...................... .............................. .............. ................................................ <br />I <br />OTHERMEMBERS........................................................................................................................1-1/2 <br />NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND <br />SLABS, WALLS. JOISTS.............................................................................:..................................3/4 <br />BEAMS,COLUMNS <br />PRIMARY REINFORCEMENT ........................................................................................................1-1/2 <br />TIES, STIRRUPS, SPIRALS........................................... ....................................... .......................... <br />I <br />ENGINEERS NOTE: ADD BA FOR SPECIAL REINFORCING CONCRETE SHEAR WALLS & MOMENT <br />FRAMES. <br />REINFORCING STEEL WELDING <br />USE ASTM A 706 GRADE 60 (fy = 60000 PSI) FOR ANY REINFORCING THAT IS TO BE WELDED. FOLLOW <br />PROCEDURES OF ANSI/AWS D1.4, "STRUCTURAL WELDING CODE - REINFORCING STEEL'. USE E 80XX LOW <br />HYDROGEN ELECTRODES CONFORMING TO ANSLAWS A5.1 OR A5.5. DO NOT WELD REINFORCING IF <br />TEMPERATURE IS BELOW 32 DEGREES FAHRENHEIT. MAINTAIN A MINIMUM PREHEAT AND INTERPASS <br />TEMPERATURE OF 50 DEGREES FAHRENHEIT FOR NO. 7 THROUGH NO. 11 BARS. DO NOT WELD NO. 14 AND <br />NO. 18 BARS. DO NOT WELD WITHIN 3-INCHES OF BENDS. LET BARS COOL NATURALLY TO AMBIENT <br />TEMPERATURE AFTER WELDING; DO NOT QUENCH. USE WABO CERTIFIED WELDERS. PROVIDE SPECIAL <br />INSPECTION PER CODE. SUBMIT MILL CERTIFICATES. <br />CONCRETE AND MASONRY ANCHORS (BOLTS, THREADED RODS AND REBAR <br />DOWELS) <br />DRILLED IN EXPANSION ANCHORS: <br />CONCRETE HILTI KWIK BOLT TZ PER ESR-1917 <br />CMU - HILTI KWIK BOLT 3 PER ESR-1385 <br />ADHESIVE ANCHORS: <br />CONCRETE HILTI HIT -RE 500.V3 PER ESR-3814 AND HILTI HIT-HY 200-R PER ESR-3187 <br />CMU HILTI HIT-HY 270 PER ESR-4143 <br />UNREINFORCED <br />MASONRY HILTI HIT-HY 270 PER ESR-4144 <br />CAST IN PLACE ANCHORS: <br />CONCRETE EMBED PER PLANS AND SECTIONS <br />CMU EMBED PER PLANS AND SECTIONS <br />SCREWANCHORS: <br />CONCRETE HILTI KWIK HU3-EZ (KH-EZ) AND HUS-EZ I (KH-EZ 1) PER ESR-3027 <br />CMU HILTI KWIK HUS-EZ <br />(KH-EZ) PER ESR-3056 <br />ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME OF <br />INSTALLATION PER ACI 318 - 14 SECTION 17.1.2 INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY <br />INCLINED TO SUPPORT SUSTAINED TENSION LOADS SHALL BE PERFORMED BY CERTIFIED PERSONNEL IN <br />CONFORMANCE TO ACI 318 -14 SECTION 17.8.2.2. <br />FOLLOW INSTALLATION PROCEDURES OF REPORT AND MANUFACTURER'S INSTRUCTIONS. PROVIDE SPECIAL <br />INSPECTION AS NOTED AND/OR REQUIRED BY'ESR REPORT. SUBSTITUTIONS <br />0 S ARE NOT ALLOWED UNLES <br />S WRITTEN <br />APPROVAL BY ENW IS RECEIVED. SUBSTITUTIONS MUST BE SUBMITTED TO ENW FOR REVIEW PRIOR TO <br />CONSTRUCTION. PROVIDE STAINLESS STEEL OR GALVANIZED ANCHORS FOR EXTERIOR APPLICATIONS AS REQUIRED. <br />ANCHORS RATED FOR DRY INTERIOR CONDITIONS MAY NOT BE USED FOR EXTERIOR APPLICATIONS PER ESR <br />REPORT. <br />STRUCTURAL STEEL <br />ALL WORK IN ACCORDANCE WITH "AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS (AISC 360-16), <br />AND THE AISC 303-16 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES" JUNE 15, 2016. <br />STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING STANDARDS: <br />WIDE FLANGE SHAPES ASTM A 992 (Fy=50,000 PSI) <br />OTHER SHAPES & PLATES ASTM A 36 (Fy=36,000 PSI) <br />TUBE SHAPES ASTM A 500, GRADE C (Fy=50,000 PSI) <br />PIPE SHAPES ASTM A 53, TYPE E OR S, GRADE B (Fy=35,000 PSI) <br />WELDHEAD STUDS ASTM A 108 (Fy=50,000 PSI) <br />ANCHOR BOLTS ASTM F 1554, GRADE 36 (Fy=36,000 PSI) <br />HIGH STRENGTH BOLTS ASTM A 325 <br />BASE PLATE GROUT ASTM C 1107 <br />BOLTS: ALL STRUCTURAL STEEL BOLTED CONNECTIONS ARE ASTM A 325 TYPE N <br />CONNECTIONS - BEARING TYPE WITH THREADS INCLUDED IN SHEAR PLANE. CONNECTIONS ARE <br />NON -SLIP CRITICAL AND BOLTS NEED TO BE TIGHTENED "SNUG TIGHT" ONLY, UNLESS OTHERWISE <br />NOTED. PROVIDE WASHERS AT OUTER PLYS WITH SLOTTED HOLES. INSTALL A 325 BOLTS IN <br />ACCORDANCE WITH'2014 RCSC SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH STRENGTH <br />BOLTS". <br />WELDS: ALL WELDING TO CONFORM WITH AWS D1.1 "STRUCTURAL WELDING CODE - STEEL". WELDS NOT <br />SPECIFIED SHALL BE W CONTINUOUS FILLET MINIMUM. ALL WELDS BY - <br />WABO CERTIFIED WELDERS. USE LOW HYDROGEN FILLER METAL WITH A MINIMUM <br />TENSILE STRENGTH OF 70 KSI. ALL WELDED JOINTS SHALL BE AWS PREQUALIFIED. <br />WELDHEAD STUDS (WMS) ARE TO BE MACHINE WELDED WITH PROPER EQUIPMENT <br />AS REQUIRED BY MANUFACTURER. <br />COORDINATE WORK WITH JOIST MANUFACTURER. SEE SPECIFICATIONS FOR ITEMS TO BE <br />GALVANIZED. ALL STEEL ERECTION, INCLUDING OPEN WEB JOISTS AND METAL DECK SHALL BE IN <br />ACCORDANCE WITH THE CURRENT OSHA STEEL ERECTION STANDARD. <br />DO NOT PLACE ANY CONSTRUCTION LOADS ON MEMBERS UNTIL THEIR CONNECTIONS ARE COMPLETE. ALL <br />STEEL NEEDS TO BE COATED FOR APPROPRIATE EXPOSURE. COORDINATE WITH ARCHITECT AND <br />ENGINEER. <br />MEMBERS DESIGNATED "POSTS" ARE NOT DESIGNED TO CARRY THE OSHA 300 POUND ECCENTRIC LOAD. <br />LIGHT GAGE STEEL FRAMING <br />STUDS AND TRACKS CONFORM WITH ASTM C 955. MATERIAL CONFORM WITH ASTM A 653, GRADE 33 FOR 18 <br />GAGE AND LIGHTER, GRADE 50 FOR 16 GAGE AND HEAVIER. GALVANIZED PER G60. SIZES AS NOTED ON <br />DRAWINGS. <br />FRAMING LUMBER <br />GRADES & STRESSES SHALL CONFORM WITH LATEST EDITION OF"WESTERN LUMBER GRADING RULES", <br />WWPA OR "STANDARD NO. 17 GRADING RULES FOR WEST COAST LUMBER", WCUB. ALL LUMBER S4S AND <br />S-DRY UNLESS NOTED OTHERWISE. <br />UNLESS NOTED OTHERWISE, USE THE FOLLOWING: <br />SPECIES <br />GRADE <br />BASE VALUE Fb <br />VISUALLY GRADED DIMENSION LUMBER <br />(2- TO 4- THICK BY 2" & WIDER) <br />STUDS -TYPICAL <br />DOUG FIR <br />STANDARD <br />525 PSI <br />STUDS - WHERE NOTED <br />DOUG FIR <br />#2 <br />900 PSI <br />JOISTS&RAFTERS- TYPICAL <br />DOUG FIR <br />#2 <br />900 PSI <br />JOISTS & RAFTERS - WHERE NOTED <br />DOUG FIR <br />#1 <br />1000 PSI <br />PLATES & LEDGERS <br />DOUG FIR <br />#2 <br />900 PSI <br />BEAMS & HEADERS -TYPICAL <br />DOUG FIR <br />#2 <br />900 PSI <br />VISUALLY GRADED TIMBERS <br />(5"X5" & LARGER) <br />BEAMS & STRINGERS <br />(WIDTH MORE THAN 2' OF THICKNESS <br />DOUG FIR <br />#1 <br />1350 PSI <br />POSTS & TIMBERS <br />(WIDTH 2" OR MORE OF THICKNESS) <br />DOUG FIR <br />#1 <br />1200 PSI <br />EACH PIECE SHALL BEAR A VALID GRADE STAMP THAT IS NOT TO BE REMOVED. BOLT HEADS AND NUTS <br />BEARING AGAINST WOOD SHALL BE PROVIDED WITH STANDARD CUT WASHERS. ALL BASE VALUE STRESSES <br />TO BE ADJUSTED WITH APPROPRIATE SIZE FACTORS. ALL WOOD IN CONTACT WITH CONCRETE OR <br />MASONRY SHALL BE PRESERVATIVE TREATED. USE STANDARD LENGTH COMMON NAILS CONFORMING WITH <br />FEDERAL SPECIFICATION FF-N-105B FOR ALL NAILING EXCEPT WHERE SHORTER NAILS PROVIDE THE <br />REQUIRED PENETRATION IN DIAPHRAGMS. <br />ALL FASTENERS, CONNECTORS, AND ANCHORS IN CONTACT WITH PRESSURE TREATED WOOD <br />SHALL BE STAINLESS STEEL, ZMAX (G185 HDG PER ASTM A653), HOT -DIP GALVANIZED <br />(HDG) PER ASTM A123 FOR CONNECTORS AND ASTM Al53 FOR FASTENERS, OR MECHANICALLY <br />GALVANIZED FASTENERS PER ASTM B695, CLASS 55 OR GREATER. <br />PROVIDE MIN. NAILING PER IBC TABLE 2304.10.1 UNLESS NOTED OTHERWISE. ALL HANGERS, TIES AND <br />CONNECTORS ARE SIMPSON. OTHER MANUFACTURERS WITH ICC-ES APPROVED LOAD CAPACITIES EQUAL <br />TO OR GREATER THAN THAT SPECIFIED MAY BE USED. NAIL ALL HOLES WITH NAILS AS SPECIFIED BY <br />MANUFACTURER. CUT NO HOLES IN ANY STRUCTURAL FRAMING WITHOUT ENGINEERS APPROVAL, EXCEPT <br />THAT 1-INCH DIAMETER HOLES MAY BE DRILLED IN 2X STUDS AND PLATES -NO MORE THAN ONE HOLE <br />EVERYB-INCHES. <br />STEEL ROOF DECK <br />VERCO PLN-3x32" WIDE -. 1-112" HIGH X 36" WIDE GALVANIZED STEEL ROOF DECK. CONFORM WITH ASTM A <br />653, SS, GRADE 50, WITH MINIMUM YIELD STRENGTH Fy=50,000 psi WITH G60 GALVANIZED COATING. <br />MATERIALS AND INSTALLATION SHALL ALSO CONFORM WITH IAPM REPORT NUMBER 2018. SEE PLAN FOR <br />DECK GAGE AND CONNECTIONS. SEE ARCH. FOR PRIME PAINT REQUIREMENTS. OTHER ROOF, DECKS AND <br />ATTACHMENT PATTERNS MAY BE CONSIDERED PROVIDED THEY HAVE AN EQUIVALENT DIAPHRAGM <br />STRENGTH AND STIFFNESS AND GRAVITY LOAD CAPACITY. ALL SUBTITUTIONS MUST BE APPROVED BY ENW. <br />SPRINKLER SUPPORT NOTES <br />1. THE FOLLOWING CRITERIA IS A MINIMUM LEVEL REQUIRED. THE FIRE PROTECTIONDESIGNER/DRAWINGS <br />MAY SET FORTH MORE STRINGENT REQUIREMENTS AT THEIR DISCRETION. REFER TO MSS DRAWINGS <br />FOR THE MAXIMUM LOAD THAT THE ROOF TRUSSES CAN SUPPORT WITH A PARTICULAR TYPE OF <br />HANGER. <br />2a. ALL SPRINKLER PIPE LARGER THAN T NOMINAL DIAMETER IS <br />TO BE CONSIDERED A "MAIN" FOR THE <br />PURPOSE OF THESE NOTES. <br />b THE BIDS FOR BOTH THE SPRINKLER & JOISTS ARE TO INCLUDE ALL HANGERS, BRACES, ETC., AND <br />ACCOUNT FOR THE LOADS INDICATED. FIRE PROTECTION DESIGNER IS RESPONSIBLE FOR <br />COORDINATING THEIR DESIGN WITH THE TYPE OF SUPPORTING MEMBERS TO BE USED FOR SUPPORT OF <br />THEIR LINES (LE. OWJ, TRUSS-PURLINS, GIRDERS, ETC.) <br />3a. ALL MAINS RUNNING PERPENDICULAR TO THE JOISTS ARE TO BE VERTICALLY SUPPORTED NO FARTHER <br />APART THAN AT EVERY OTHER JOIST (I.E. 10 FEET). - <br />h. EACH JOIST THAT IS CROSSED BY A MAIN IS TO BE DESIGNED FOR THE VERTICAL SUPPORT LOAD BASED <br />ON SUPPORTS AT EVERY OTHER JOIST. <br />4. ALL MAINS RUNNING PARALLEL TO THE JOISTS MUST BE: <br />a. PLACED MID -WAY BETWEEN TWO JOISTS & BE TRAPEZED SO EACH JOIST SUPPORTS <br />HALF THE LOAD. - <br />b. SUPPORTED AT 10'-0" O/C MAXIMUM. <br />5. USE THE FOLLOWING WEIGHTS FOR SPRINKLER VERTICAL SUPPORT DESIGN: <br />PIPE WE PER <br />SIZE FOOT VERTICAL JOIST LOAD EXAMPLE: <br />S. 51# GIVEN: 8" DIAMETER MAIN TRUSSES @ V O/C <br />6" 32# FIND: JOIST DESIGN LOAD <br />5" 24# SOLN: 51#/FT X 10' = 510# <br />4" 17# ADDN'L PER NFPA #13 = 250# <br />3-1/2" 14# 760NHGR <br />ALL HANGERS TO BE DESIGNED, SUPPLIED & INSTALLED BY THE SPRINKLER SUPPLIER. <br />6. SPRINKLER LATERAL SWAY BRACING, FOR SEISMIC DESIGN CATEGORY C, D, E, F (AT 90 DEGREES TO <br />2-1/2" NOM. DIA. & LARGER PIPE) TO BE: <br />a. SPACED A MAXIMUM OF 40 FT. OR AS ALLOWED BY N.F.P.A. #13. <br />b. BRACED FROM THE MAIN TO A ROOF STRUCTURAL MEMBER WITH CONNECTIONS DESIGNED & INSTALLED <br />BY THE SPRINKLER SUPPLIER. <br />c. DESIGNED FOR A LATERAL LOAD OF THE WEIGHT PER FOOT OF WATER FILLED PIPE TIMES THE SWAY <br />BRACE SPACING, PLUS THE WEIGHT OF TRIBUTARY BRANCH LINE WATER FILLED PIPE. <br />J. CROSS MAIN BRACING MUST BE ADEQUATELY FASTENED TO THE MAIN FRAME BEAMS. <br />7. THE SPRINKLER DESIGNER IS TO PROVIDE THE CONTRACTOR, ARCHITECT, ENW & THE ROOF SUPPLIER <br />WITH LOCATIONS AND DETAILS OF HANGER AND SWAY BRACE ATTACHMENTS WITH THEIR DESIGN <br />LOADS, SO THESE LOADS CAN BE DESIGNED INTO THE JOISTS, ETC. <br />B. THE SPRINKLER CONTRACTOR/DESIGNER SHALL SUBMIT: <br />a. PLAN WITH LOCATIONS AND LOADS OF ALL HANGERS. <br />b. DETAILS AND CAPACITIES OF ALL HANGERS USED. <br />9. THE MBS ROOF DESIGNER TO PROVIDE & INSTALL ADDITIONAL BRACES TO TAKE THE SWAY BRACE LOAD <br />FROM THE SWAY BRACE INTO THE ROOF LATERAL RESISTING SYSTEM. <br />NOTE TO MECHANICAL AND ELECTRICAL TRADES <br />CONTRACTOR SHALL SUBMIT PLANS SHOWING LOCATION, LOAD AND ANCHORAGE OF ALL HANGERS <br />SUPPORTING ANY MECHANICAL, ELECTRICAL, PLUMBING OR SPRINKLER LOADS IN EXCESS OF 50 POUNDS. <br />ANY ROOF MOUNTED EQUIPMENT SHALL BE INCLUDED IN THESE. PLANS AND SHALL SHOW LOADS AND <br />LOCATIONS. THESE SHALL BE SUBMITTED TO ENGINEERS NORTHWEST FOR APPROVAL PRIOR TO <br />INSTALLATION OF ANY OF THIS EQUIPMENT. ALL DETAILS OF CONNECTIONS TO THE STRUCTURE FOR <br />EQUIPMENT SHALL BE BY THE SUPPLIER OF THAT EQUIPMENT. IF THE BUILDING DEPARTMENT REQUIRES A <br />SUBMITTAL REGARDING THE DESIGN OF THESE DETAILS, IT WILL BE THE RESPONSIBILITY OF THE <br />EQUIPMENT SUPPLIER TO PROVIDE THIS SUBMITTAL. <br />SPECIAL CONDITIONS <br />CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND SHALL PROVIDE ADEQUATE SHORING AND <br />BRACING OF ALL STRUCTURAL MEMBERS DURING CONSTRUCTION. CONTRACTOR SHALL NOTIFY ENGINEER <br />OF ALL FIELD CHANGES PRIOR TO INSTALLATION. <br />SHOP DRAWINGS <br />SUBMIT 4 SETS OF PRINTS (U.N.O. BY ARCHITECT) OR ELECTRONIC PDF FILES, OF SHOP DRAWINGS TO <br />ENGINEER FOR REVIEW AFTER CONTRACTOR HAS REVIEWED & STAMPED FOR COMPLIANCE AND PRIOR TO <br />FABRICATION FOR: STRUCTURAL STEEL, MISCELLANEOUS STEEL, AND REINFORCING STEEL. WHEN SHOP - <br />DRAWING SUPPLIER MAKES A CHANGE FROM THE CONTRACT DRAWINGS IT IS TO BE CLEARLY FLAGGED <br />AND CLOUDED. CHANGES NOT FLAGGED AND CLOUDED ARE TO BE CONSIDERED AS UNACCEPTABLE EVEN <br />WITHOUT BEING COMMENTED ON IN THE SHOP DRAWING REVIEW PROCESS. THE SUPPLIER OF THE ITEM <br />CONTAINING THE CHANGE SHALL BE RESPONSIBLE FOR CHANGING THE ITEM BACK TO AGREE WITH THESE <br />DRAWINGS AT NO COST TO THE OWNER AT E.N.W.'S OPTION. "SHOP DRAWINGS ARE AN ERECTION AID, AND <br />STRUCTURAL DRAWINGS SHALL TAKE PRECEDENT OVER THE SHOP DRAWINGS...". <br />SPECIAL INSPECTIONS AND TESTS <br />INSPECTIONS ARE TO BE PER IBC CHAPTER 17 AND ARE TO BE BY AN INDEPENDENT TESTING AGENCY. THE <br />SPECIAL INSPECTION AGENCY AND SPECIAL INSPECTION INSPECTORS SHALL BE REGISTERED WITH THE <br />WASHINGTON ASSOCIATION OF BUILDING OFFICIAL (WABO), AND SHALL BE APPROVED BY THE BUILDING <br />OFFICIAL PRIOR TO CONSTRUCTION. SEE SPECIAL INSPECTION TABLES ON SHEET S0.2. <br />OTHER INSPECTIONS <br />BY BUILDING OFFICIAL IN ACCORDANCE WITH SECTION 110 OF IBC. <br />PRECAST PANEL NOTES <br />1. PANEL ELEVATIONS SHOW INSIDE FACE. <br />2. CONTRACTOR TO VERIFY ALL DIMENSIONS IN FIELD PRIOR TO FORMING PANELS. <br />3. PROVIDE ADDITIONAL HORIZONTAL REINFORCING PER PANEL ELEVATIONS AT OPENINGS WITH <br />HORIZONTAL TRIM BARS EXTENDING 2'-0" BEYOND EDGE OF OPENINGS U.N.O. VERTICAL TRIM BARS TO <br />RUN FULL LENGTH U.N.O. <br />4. PANEL LIFTING STRESSES ARE TO BE CHECKED BY THE CONTRACTOR WHO SHALL PROVIDE <br />REINFORCING STEEL AS REQUIRED FOR HANDLING AND ERECTION. USE STRONGBACKS AS REQUIRED AT <br />EXCESSIVE PANEL OPENINGS. <br />S. PROVIDE 3/4" CHAMFER AT ALL EXPOSED CORNERS UNLESS OTHERWISE INDICATED ON ARCHITECTURAL <br />DRAWINGS. <br />6. PROVIDE 3 COATS ASPHALTIC PAINT OR A 3" MINIMUM CONCRETE COVER AT ALL STEEL CONNECTIONS <br />EXPOSED TO EARTH OR WEATHER. <br />7. PROVIDE 3/4" NON -SHRINK GROUT BETWEEN BOTTOM OF PRECAST PANELS AND TOPS OF FOOTINGS. <br />8. MAXIMUM DEPTH OF REVEAL STRIPS TO BE 3/4". SEE ARCHITECTURAL DRAWINGS FOR LOCATION. <br />VERIFY ALL PANEL THICKNESSES WITH ARCHITECTURAL DRAWINGS. <br />9. PANEL CONNECTIONS FOUND ON S4.XX SERIES SHEETS, <br />10.PROVIDE 1/2" CLEARANCE BETWEEN PRECAST ELEMENTS UNLESS NOTED OTHERWISE. <br />11.SHOP DRILL (1/4" DIAMETER) AIR RELEASE HOLES IN EMBEDMENTS AT 8" o/c AS REQUIRED IN ORDER TO <br />DISPLACE ANY VOIDS IN FORMWORK. <br />12.REMOVE ALL WELD SLAG AROUND EMBEDMENTS EXPOSED TO WEATHER AND SAND -BLAST. PROMPTLY <br />PAINT WITH 2 COATS OF RUST INHIBITING PRIMER PRIOR TO FINAL PAINTING. <br />13.TYPICAL PANEL TO BE 8 1/2 THICK UNLESS NOTED OTHERWISE. PLACE VERTICAL REINFORCING AT <br />CENTERLINE OF PANEL UNLESS NOTED OTHERWISE. WHERE REINFORCING STEEL IS NOTED AS E.F. <br />(EACH FACE), PLACE 314"CLEAR TO INSIDE FACE AND 1-1/2" CLEAR TO OUTSIDE FACE. REFER TO SHEET <br />55.1 FOR DETAILS. <br />ABBREVIATIONS <br />L.L.H. <br />LONG LEG HORIZONTAL <br />ARCH. <br />ARCHITECT <br />L.L.V. <br />LONG LEG VERTICAL <br />BAL. <br />BALANCE <br />M.F.R. <br />MANUFACTURER <br />B. OR BOT. <br />BOTTOM <br />M.O. <br />MASONRY OPENING <br />N. BTW <br />BETWEEN <br />N.F. <br />NEAR FACE <br />BLDG. <br />BUILDING <br />N.T.A. <br />NOT TO SCALE <br />BRIG. <br />BEARING <br />oc <br />ON CENTER <br />C.I.P. <br />CAST IN PLACE <br />O.F. <br />OUTSIDE FACE <br />C.J. <br />CONSTRUCTION JOINT - .. <br />O.S. <br />OUTSIDE <br />CL <br />CENTERLINE <br />O.T.O. <br />OUT TO OUT <br />CUR. <br />CLEAR <br />P.P.T. <br />PRESERVATIVE <br />CMU <br />CONCRETE MASONRY UNIT <br />PRESSURE TREATED <br />COL <br />COLUMN <br />PLATE <br />CONC. <br />CONCRETE <br />REINFORCING <br />C.S.J. <br />CLOSURE STRIP JOINT <br />REMAINDER <br />D.F. <br />DOUGLAS FIR <br />ROUGH OPENING <br />EA <br />EACH <br />SECTIONS <br />E.E. <br />EACH END <br />SIMILAR <br />E.F. <br />EACH FACE <br />SHRINKAGE JOINT <br />E.J. <br />EXPANSION JOINT <br />STEEL <br />EL OR ELEV. <br />ELEVATION <br />SHEARWALL <br />E.N.W. OR ENW <br />ENGINEERS NORTHWEST <br />SYMMETRICAL <br />EQ. <br />EQUAL <br />TOP <br />E.S. <br />EACH SIDE <br />TOP OF <br />E.W. <br />EACH WAY - <br />TOP OF BEAM <br />F.O. <br />FACE OF <br />TOP OF FOOTING <br />F.O.C. <br />FACE OF CONCRETE <br />TOP OF STEEL <br />F.O.S. <br />FACE OF STUD <br />TOP OF SLAB <br />F.O.W. <br />FACE OF WALL <br />SIMILAR PLACES <br />FTG. <br />FOOTING <br />TOP OF WALL <br />GA. <br />GAGE <br />TYPICAL AT ALL <br />GALV. <br />HOT DIP GALVANIZED <br />UNLESS NOTED OTHERWISE <br />G.L.B. <br />GLU-LAM BEAM <br />VERTICAL EACH FACE <br />G.W.B. <br />GYPSUM WALL BOARD <br />VERTICAL <br />H. OR HORIZ. <br />HORIZONTAL <br />VERTICAL FAR FACE <br />H.F. <br />HEM -FIR <br />VERIFY <br />H.S.S. <br />HOLLOW STRUCTURAL SECTION <br />VERTICAL INSIDE FACE <br />I.B.C. <br />INTERNATIONAL BUILDING CODE <br />VERTICAL NEAR FACE <br />I.C.C. <br />INTL. CODE COUNCIL <br />VERTICAL OUTSIDE FACE <br />I.F. <br />INSIDE FACE <br />WITHINC. <br />INCLUDING <br />WITHOUT <br />I.S. <br />INSIDE FACE <br />W.H.S. <br />WELD HEAD STUD <br />K <br />KIP (1000 POUNDS) <br />AT CENTER LINE <br />L.W. <br />LONG WAY <br />PLATE <br />PL <br />REINF. <br />REM. <br />R.O. <br />SECT. <br />SIM. <br />S.J. <br />STL. <br />SW <br />SYM_ M. <br />T. <br />T.O. <br />T.O.B. <br />T.O.F. <br />T.O.S. <br />Fire <br />T.O.W. <br />NP. <br />U.N.O. <br />V.E.F. <br />VERT. <br />V.F.F. <br />VFY <br />V.I.F. <br />V.N.F. <br />V.N.F. <br />wl <br />w/o <br />�j <br />Permit tF: <br />B2204048 ROLLED PLANS <br />(STRUCTURAL RECO 8/29/22) <br />Site Address: <br />1235 MYTH SrSW <br />Owner: <br />SMARTCAP BAKER VIEW LOGISTICS CENTER <br />LLC <br />Tenant <br />BAKER VIEW LOGISTICS CENTER <br />APP-Date: <br />4/23/2022 <br />Proposed Use: <br />NEW COMMERCIAL <br />DesQiplian: <br />NEW 166,5905E WAREHOUSE OEMBLDG <br />SHELLONLY ZR <br />Reviewed By: <br />7CG"Date: <br />OfficeSet <br />Job Site Set <br />p GC�C�OdCC <br />AUG 29 <br />2022 <br />CITY OF EVERETT <br />Permit Services <br />CONCRETE REINFORCING <br />SPLICE SCHEDULE <br />BAR SIZE <br />3000P51 LAP <br />4000/4500 PSI LAP <br />#3 <br />20" <br />17" <br />#4 <br />26" <br />23" <br />#5 <br />33" <br />28" <br />#8 <br />39" <br />34" <br />#7 <br />57" <br />49" <br />#8 <br />65" <br />56" <br />#9 <br />73" <br />63" <br />#10 <br />82" <br />71" <br />#11 <br />81" <br />78" <br />STRUCTURAL CONCRETE: TYPE I / II CEMENT <br />LOCATION <br />EXPOSURE <br />MINIMUM 28 <br />MAXIMUM AIR <br />LIMITS ON <br />CEMENT TYPE <br />MAX. WATER-SOLUBLE CHLORIDE <br />CLASS <br />DAY STRENGTH <br />W/C RATIO <br />CONTENT <br />CEMENTITOUS <br />ASTM C150 <br />ION CEMENT IN CONCRETE % BY <br />MATERIALS <br />WEIGHT OF CEMENT <br />INTERIOR WALLS <br />FO/SO/WO/CO <br />4000 PSI <br />0.49 <br />N/A <br />N/A <br />I / II <br />1.00 <br />EXTERIOR WALLS <br />F2/S0/1V0/C1 <br />4500 PSI <br />0.45 <br />ACI 318-14 <br />N/A <br />I / II <br />0.30 <br />TABLE 19.3.3.1 <br />EXTERIOR SLABS, <br />F2/SOAM)/C1 <br />4500 PSI <br />0.45 <br />ACI 318-14 <br />N/A <br />I / II <br />0.30 <br />FOOTINGS <br />TABLE 19.3.3.1 <br />