Laserfiche WebLink
Seatronics, Inc. Boeing 40-27 Elevator project Section 1 <br /> Job: 10403203 Fire Alarm System Submittal Manual Page 2 <br /> SYSTEM SEQUENCE OF OPERATION <br /> A. ELEVATOR <br /> 1. ALARM CONDITIONS - ELEVATOR LOBBIES: <br /> 1.1 ACTIVATION OF SMOKE DETECTOR(S) ON THE FLOOR 2 LOBBY SHALL CAUSE THE <br /> FOLLOWING TO OCCUR: <br /> A. ILLUMINATE THE RED "ALARM" INDICATOR ON THE FAP. <br /> B. DISPLAY MESSAGE ON THE CONTROL PANEL LCD DISPLAY INDICATING LOCATION <br /> INFORMATION FOR THE DEVICE THAT WAS ACTIVATED. <br /> C. ACTIVATE ALARM BELL UNIT(S) IN ELEVATOR LOBBIES. <br /> D. TRANSMIT AN "ALARM" SIGNAL TO THE REMOTE MONITORING STATION. <br /> E. RECALL ELEVATOR TO PRIMARY FLOOR (FLOOR 1). <br /> F. ACTIVATE HVAC SHUT DOWN. <br /> 1.2 ACTIVATION OF SMOKE DETECTOR ON THE 1ST FLOOR ELEVATOR LOBBY SHALL CAUSE <br /> THE FOLLOWING TO OCCUR: <br /> A. ILLUMINATE THE RED "ALARM" INDICATOR ON THE FAP. <br /> B. DISPLAY MESSAGE ON THE CONTROL PANEL LCD DISPLAY INDICATING LOCATION <br /> INFORMATION FOR THE DEVICE THAT WAS ACTIVATED. <br /> C. ACTIVATE ALARM BELL UNIT(S) IN ELEVATOR LOBBIES. <br /> D. TRANSMIT AN "ALARM" SIGNAL TO THE REMOTE MONITORING STATION. <br /> E. RECALL ELEVATOR TO THE ALTERNATE FLOOR (FLOOR 2). <br /> F. ACTIVATE HVAC SHUT DOWN. <br /> 2. ALARM CONDITIONS - MACHINE ROOM & HOISTWAY <br /> 2.1 ACTIVATION OF A SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM OR TOP OF <br /> HOISTWAY SHALL CAUSE THE FOLLOWING TO OCCUR: <br /> A. ILLUMINATE THE RED "ALARM" INDICATOR ON THE ELEVATOR FAP. <br /> B. DISPLAY MESSAGE ON THE CONTROL PANEL LCD DISPLAY INDICATING LOCATION <br /> INFORMATION FOR THE DEVICE THAT WAS ACTIVATED. <br /> C. ACTIVATE ALARM BELL UNIT(S) IN ELEVATOR LOBBIES. <br /> D. TRANSMIT AN "ALARM" SIGNAL TO THE REMOTE MONITORING STATION. <br /> E. RECALL ELEVATOR TO THE PRIMARY FLOOR (FLOOR 1) <br /> F. ACTIVATE ELEVATOR FLASHING FIRE-HAT CONTROL. <br /> G. ACTIVATE HVAC SHUT DOWN. <br /> 2.2 ACTIVATION OF A HEAT DETECTOR IN THE ELEVATOR MACHINE ROOM OR TOP OF <br /> HOISTWAY SHALL CAUSE THE FOLLOWING TO OCCUR: <br /> A. ILLUMINATE THE RED "ALARM" INDICATOR ON THE ELEVATOR FAP. <br /> B. DISPLAY MESSAGE ON THE CONTROL PANEL LCD DISPLAY INDICATING LOCATION <br /> INFORMATION FOR THE DEVICE THAT WAS ACTIVATED. <br /> C. ACTIVATE ALARM BELL UNIT(S) IN ELEVATOR LOBBIES. <br /> D. TRANSMIT AN "ALARM" SIGNAL TO THE REMOTE MONITORING STATION. <br /> E. ACTIVATE ELEVATOR POWER SHUNT TRIP BREAKER (SHUTDOWN POWER TO <br /> ELEVATOR). <br /> F. ACTIVATE HVAC SHUT DOWN. <br /> Seatronics, Inc. PO BOX 1138 Auburn, WA 98001 253-939-6060 <br />