Mr. Jeffery Kildare <br /> Plan Check Number: B2209-004 Second Building Review <br /> March 15, 2023 <br /> Architectural <br /> 1. Energy credits are required per WSEC Section R406. The required number of credits should be <br /> normalized per Table R406.2 of the 2018 WSEC. The provided credit selection is from the 2015 <br /> WSEC. Please revise the schedule of the selected credits and include the schedule in the <br /> drawings. The performance requirements for the selected credits should be specified. For <br /> reference, the 2018 Single Family Prescriptive Worksheet has been attached. <br /> 2. The project requires a whole house ventilation system per IRC Section R303.4. Show the <br /> location on the plans; the fan should not be located inside a closed room. Specify the <br /> performance requirements per Section M1505.4. <br /> 3. Window 6 (see Sheet A101) should be safety glazed if the bottom exposed edge of the glazing <br /> is less than 60" measured vertically from the walking surface. Please specify safety glazing or <br /> show or provide the vertical measurements showing the safety glazing exception. See IRC <br /> R308.4.5. <br /> 4. The direct clearance in front of the powder room toilet and the vanity should be 21" per <br /> R307.1. <br /> 5. The enclosed space under stairs should be enclosed with no less than 1/2" gypsum wall board. <br /> See Sheet A101 and IRC Section R302.7. <br /> 6. The eave projection on the West wall appears to be within the 5'fire-separation distance. Per <br /> IRC Table R302.1(1) projections 2'to 5' within the fire-separation are required to be fire- <br /> resistance rated to a minimum of 1 hour on the underside, or fire-retardant-treated wood. <br /> Structural <br /> 1. The proposed project includes structural work. Structural drawings should be submitted as <br /> needed that include framing plans, sections, details, construction schedules, fastening <br /> schedules, materials requirements, general notes, special inspection requirements, etc. The <br /> drawings should substantiate compliance with the prescriptive requirements of the IRC. See <br /> IRC Sections R106.1.1 and R301.1. <br /> 2. The proposed design includes wall bracing that may or may not comply with the requirements <br /> of IRC Section R602.10. The drawings should be revised to show proposed wall bracing. See <br /> IRC Section R106.1.3. Alternatively, an engineered analysis and design may be performed per <br /> IRC Section R301.1.3; sealed and signed drawings and calculations prepared by a professional <br /> engineer licensed in the state of Washington are required per RCW 18.43.010, 18.43.020, and <br /> 18.43.070. <br /> 0 3200 Cedar Street © 425.257.8810 O permitservices@everettwa.gov <br /> Everett, WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 2 of 3 <br />