Micah Diamond <br />Carriage Houses Northwest <br />Plan Check Number: B2109-049, First Building Review <br />October 13, 2021 <br />6. Plans should provide a detail of the interior footing. Detail should also show connection of post <br />to footing and footing reinforcement. R106.1.1, R403.1.3.5 <br />7. See Typical Wall Section on Sheet 3. Provide framing information showing how lateral forces <br />are transferred from roof diaphragm into brace/shear wall and connections from floor to floor. <br />8. Continuing with the precious comment, it is unclear how the PWI roof joist are attached to the <br />wall top plate. Note that the wall top plate appears not to be placed flat on top of the wall. <br />Please refer to the manufacturers framing details and provide web stiffeners where required. <br />R106.1.1 <br />9. See Typical Wall Section on Sheet 3. Plans should specify the washer size to be 0.229 inch by 3 <br />inches x 3 inches in size per IRC Sec. R602.11.1. <br />10. See Roof Framing Plan on Sheet 1. It appears that the roof sheathing cantilevers V-6". A detail <br />or framing should be shown to support the cantilever. Note the maximum cantilever for roof <br />sheathing beyond the gable end wall is 9" unless supported by gable overhang framing. See <br />Section R802.5.2.1 <br />11. See Detail Garage LRP on Sheet 3. It appears that a portal frame type of braced wall is <br />provided. The detail should specify the type of brace wall. See Section R602.10 for brace wall <br />requirements and incorporate all requirements into the detail and plans. R106.1.1 <br />12. See Page 3. The design wind speed should be 85 mph per EMC Section 16.01.010(J). <br />13. See Typical Wall Section on Page 3. Footing reinforcement cover should be specified per Section <br />R403.1.3.5.3. <br />This review has been performed for general compliance with the building codes as adopted and <br />amended by the state of Washington and the city of Everett. Corrections and comments made <br />during the review process do not relieve the project from compliance with code and permit <br />requirements. The designers -of -record are responsible for a complete design in accordance with <br />the laws of the state of Washington. <br />If you have any questions or require additional clarification, please contact us. <br />Respectfully, <br />Rakeeb Khan <br />Residential Plans Examiner <br />(425)257-7299 <br />rkhan@everettwa.gov <br />S:\RKhan\2021\B2109-049—R1.docx <br />3200 Cedar Street © 425.257.8810 O everetteps@everettwa.gov <br />Everett, WA 98201 425.257.8857 fax everettwa.gov/permits <br />Page 3 of 3 <br />