Laserfiche WebLink
Port Gardner Storage Facility Volume 7 Attachment O <br /> Page 12 <br />CITY OF EVERETT ⋅ 3200 Cedar Street ⋅ Everett, WA 98201 ⋅ (425) 257-8800 ⋅ Fax (425) 257-8882 <br /> <br />Q56 - Specification 02 41 00 3.04 DEMOLITION A states “The contractor shall be <br />responsible for determining the scope and extent of the required work by inspecting the <br />site prior to submittal of bid.” Please confirm that if demolition beyond the limits shown <br />in the drawings is required to construct the Work, Article 6 CHANGES will apply for <br />compensation. <br />The linear demolitions shown in the drawings do not have finite limits. For <br />example, the end of pipe and/or duct bank, buried electrical lines, etc. are <br />approximate and may have to be extended to permit installation of new facilities. <br />This is noted in General Note 8 on Drawing CX-10-2002, CX-10-2003, and CX-10- <br />2004. Further, paragraph 3.04.E of the specification in question also notes the <br />necessity to remove piping and duct bank from areas indicated on the drawings <br />and as necessary to install new facilities. Hence, demolition beyond the linear <br />limits do not fall under Article 6 Changes. In addition, per Specification 02 41 00 <br />3.04, paragraph 3.04.C states that the drawings define minimum portions of <br />facilities and structures to be removed. Therefore, if some additional <br />demolition/removal is needed to install new facilities, it would not fall under <br />Article 6 Changes. <br />Also, if existing buried structures, piping, duct bank, electrical conduit and cables <br />not shown on record drawings are discovered during construction that differ <br />materially from the drawings and specifications, this may be addressed under <br />General Conditions Article 11 Differing Site Conditions. <br />Q57 - Drawing CD-10-7001, Detail L, indicates a 36”x36” hatch for the precast utility <br />vault. Note 1 says the assembly will be installed in a non-traffic area. Shall it conform <br />to Specification 08 31 20 and are they (2 each) any of the ones listed in the Floor <br />Access Door Schedule in Section 3.06? <br />The 36”X36” hatches are not included in the Section 3.06 table. The hatch per <br />detail L should be load rated 300 psf minimum, as specified in Section 08 31 20. <br />Q58 - Drawings C-10-1203 and C-10-6201 show SWVT 46-06 in plan and profile <br />respectively, but no apparent reference to construction details (precast or CIP). Please <br />provide. <br />SWVT 46-06 is a packaged pump station that shall meet Specification 33 32 16. <br />Q59 - Please reference drawing D-40-1001. Drawing D-40-1001 shows a 6” SW line <br />connecting to an existing concrete box. No penetration details are listed. Please advise <br />if the penetration already exists or if one should be included in this bid. If so, please <br />provide the penetration detail type. <br />There is an existing penetration from the concrete box to connect the new 6" SW. <br />No new penetration is required. <br />