Laserfiche WebLink
s � • <br /> The blocking called out in the typ. Wall section should be clearly detailed. The drawing <br /> calls out"2x4 studs 16"O.C., hold away from conc wall 1/2" t. <br /> "Section A"shows 2x4's placed flat on the wall? This orientation will not provide <br /> structural benefit. <br /> 7. Provide egress window in master bedroom. Specify maximum 44"to bottom of opening <br /> (not sill height) per R310 IRC. <br /> NOTE: If single sheet(s) are replaced in plan set it is applicants responsibility to replace <br /> sheets in drawing set. Please allow time to perform this task. <br /> Please prepare a response letter showing where each item in this correction <br /> letter is addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: iheilman@ci.everett.wa.us <br /> t� <br /> S:\1Common\Clerical\]Heilman\CW1502-002(3617 Geyer Ln)#2.doc <br />