5. Please dimension tosetback dimension of the extended n9deck and new wall from <br /> the property line. <br /> a. Fire resistant construction should be shown on the drawings as required by IBC <br /> Table 602 and IBC Table 705.8 at property line setbacks. <br /> New and modified exterior walls should be shown on the drawings to comply with WSEC <br /> Table R402.1.1 (new walls) and R101.4.3, exception 3 (exposed cavities) for energy <br /> requirements. ew d k� <br /> a. The'roof should be shown on the drawings with R-49 insulation. <br /> 7. New guards should be detailed on the drawings per IBC sections 1012 and 1013 for the <br /> new deck, to show height, maximum clear openings, and structural detailing to resist 50 <br /> pound per linear foot and a concentrated load of 200 pounds, per IBC 1607.8.1, <br /> 8. Handrails meeting the minimum requirements of the IPMC should be shown at all <br /> existing stairs, at least on one side of the stair run, per IPMC 307.1. <br /> 9. Where windows are replaced, egress windows should be dimensioned, and window <br /> locks should be shown on the drawings for new windows, per IBC sections 1029 and <br /> 1013.8. <br /> a. All new windows should be identified on the drawings with at least a .30 U <br /> factor, per WSEC table R402.1.1. <br /> b. New windows are required to provide outside air per IMC 403.8.3. <br /> 10. Where exterior egress doors are replaced due to fire or water damage to the structure, <br /> minimum one leaf of the door opening should be shown to have minimum 32 clearance <br /> between the face of the door and the stop, per IBC section 1008.1.1. This typically <br /> requires a minimum 2 foot 10 inch door leaf. <br /> a. New exterior doors should be identified on the drawings with minimum U-factor <br /> shown in WSEC table R303.1.3 (2), based on the percent glazing of the door. <br /> 11. Smoke and carbon monoxide detectors should be shown on the drawings per IBC <br /> sections 907.2.11.2 and 908.7, as amended by the State of Washington. <br /> a. Hardwired interconnected smoke detectors are required where the ceilings have <br /> been removed due to fire and water damage. <br /> 12. Where toilet room ceilings are being replaced, new toilet room exhaust fans should be <br /> shown on the drawings to be ducted directly to the outside, meeting the minimum <br /> requirements of 50 cfm intermittent operation, or 20 cfm continuous operation, <br /> maximum 1 sonne. <br /> 13.The new laundry room should indicate a whole house fan to meet minimum <br /> requirements of current code, per IMC 403.8.1 and dryer exhaust per IMC 504. <br /> All codes cited refer to the 2012 International Residential Code (IRC), 2012 International <br /> Property Maintenance Code (IPMC), 2012 International Building Code (IBC), the 2012 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8800 • Fax(425) 257-8882 <br />