� <br />C � <br />f 2. Maximum exit access travel distance is 250 feet, per IBC table 1021.2(2). Common path of <br />� travel will require that an exit is available within 75 feet, per IBC table 1014.3. <br />a. Please show the path of travel for both exits required from the assembly space on the <br />second floor to the exit discharge on the first floor. <br />The door schedule should show numbered doors on the plan for egress for this permit only. <br />a. A sign should be posted by the main exterior doors required for egress that the door is <br />to remain unlocked when the building is occupied. IBC section 1008.1.9 <br />b. Panic hardware is required for assembly occupancies with greater than 49 occupants <br />from the room containing the assembly use to the exit discharge, with the exception for <br />a main exit as noted, per IBC section 1008.1.10. <br />Emergency lighting should be shown on the drawings from the assembly use to the exit <br />discharge, per IBC section 1006.1. <br />Illuminated exit signs should be shown on the drawings from the assembly use to the exit <br />discharge, per IBC section 1011.1. <br />Construction <br />1. All walls and doors in the tenant space should be indicated as new on the drawings, unless <br />V� previously permitted, inspected, and approved <br />a. Wall construction should be detailed <br />ti��� horizontal load. <br />���� cce s�b'i�l��� <br />�,�� � <br />�� ��.. The purpose of the ne as� bly use should <br />�1�r,� unique to the building, th ,�i a new elevator to <br />��y sections 3411.4.1, 3411,6, 3`�1.7, 3411.8 and <br />(finaled). <br />on the drawings to resist a minimum 5 psf <br />be explained on the drawings. If the purpose is <br />access the second floor will be required, per IBC <br />1104.4 exception 1, and 1108.2.1. <br />� <br />���,+(r�Additional Comments • <br />��` ���1. Mechanical, plumbing, suppression, and electrical permits can be obtained after the building <br />��r, 3` ��� permit is issued. <br />� <br />���� These comments address building issues only. Revisions or additions may be required by other <br />departments (Utilities, Public Works, Tra�c, or Planning). Upon resubmission of the drawings, plan <br />review will resume and your application will be given priority. All required submittals must be of <br />sufficient detail and information to ensure that the proposed structure will be constructed in compliance <br />with all a.dopted codes. Code references cited include the 2012 International Building Code (IBC), 2012 <br />International Fire Code (IFC), and the 2012 International Property Maintenance Code (IPMC). The <br />current IBC referenced standard for accessible design is the 2009 "Accessible and Usable Buildings and <br />Facilities" (ICC/ANSI A117.1). Federal ADA regulations and standards may be more restrictive. All codes <br />referenced, as adopted by the City of Everett, must include current revisions by the State of <br />Washington. <br />Sinc rel ' <br />Meg Hal y, <br />Plan Revi Architect, 425-257-8813 <br />Cc: Lauren Bivins, Harbor Marine; AFM Jim Venturo, City of Everett �J <br />