Laserfiche WebLink
. � (' <br /> 7. Double-acting doors should be provided with view panels of not less than 200 square <br /> inches, with the bottom edge located no higher than 43" above the floor. Sections <br /> 1003.3.1.5& 1106.10.7 <br /> Accessibility <br /> 1. Areas of evacuation assistance and all their details such as size, locadon,telephone, <br /> fire protection, signs,etc. should br. shown. 48" cleaz width beriveen handrails in <br /> each stairway is also required for evacuation. Section 1104. Note that is the <br /> exception is requested,a note should be shown on the plans that quick-response <br /> sprinkler heads aze required throughout the building,and the fire-and life-safety <br /> emergency evacuation plan should be submitted to this office. <br /> Energy <br /> 1. The perimeter slab insulation should be shown between the slab and exterior wall to <br /> provide a thermal break. Section 1311.5 . � <br /> I <br /> Prepare a response letter showing where each item in this coaection letter is addressed <br /> on the plan set. <br /> Upon resuLmitai of the drawings, your application will be given priority and plan review , i <br /> will commence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to <br /> ensure that the proposed structure will be constructed in compliance with all adopted ' <br /> codes. <br /> Sincerely, I <br /> ��� <br /> Tony I.ee <br /> Assoc;iate Engineer <br /> 77.:jt:660795 <br />