Laserfiche WebLink
e. Handrail details (hcight, design and attachment) where ramp <br />exceeds 6 inches above adjacent grade, per ICC/ANSI A117.1- <br />2003 section 405.8. <br />f. Handrails on the ramp require edge protection of an additional <br />lower raif or extended surface, per ICC/ANSI A117.1 Section <br />405.9. <br />g. Landings should be indicated on the drawings as having a <br />minimum dimension in the direction of travel of 60 inches. <br />lO.Curb ramps on Che actessible routes should be shown or referenced on <br />the drawings per ICC/ANSI Ai17.1-2003 section 406. <br />?.1.Call controls, sianage, visible, and audible signals should be shown on <br />the drawings to comply with ICC/ANSI A117.1-2003 section 407.2 and <br />IBC section 1101.2.10, with the exception of section 407.4.6.2.2, Fer <br />IBC section 1101.2.4 as amended by Washington SYate. <br />12.The men and women toilet rooms 162 and 163 require 60 inch clear <br />space behveen the edge of the lavatory and the wall parallel to the <br />water closet, per ICC/ANSI A117.1-2003 section 664.3.1. <br />13.The reyuired clearance at accessible water closets should be <br />dimensioned (inside clear), per ICC/ANSI A117.1-2003 section <br />604.3.2. <br />14.7he turning space within the toilet rooms should be dimensioned, per <br />ICC/ANSI A117.1-20G3 section 603.2.1. <br />15.On pian detail 1/A401, the cenYerline of the women's room accessiblc� <br />water closet should be dimensioned as between 16 and 18 inches from <br />the side wall, per ICC/ANSI A117.1-2003 section 604.2. The location <br />of all water closets in the clinic shnuld be dimensioned on the <br />drawings. <br />16.Tha vertical grab bar should be shown in elevation in the accessible <br />water closet compartment, per ICC/ANSI A117.1-2003 section 604.5. <br />All grab bar dimensions (vertical and horizontal) should be shown on <br />the drawings to comply with per ICC/ANSI A117.1-2003 figure <br />604.5.1. <br />17. The toilet paper dispenser in the accessible water closet compartmen': <br />sho��id be shown on the drawings to comply with ICC/ANSI A117.1- <br />2003 section 604.7. <br />18.The lavatory height shuuld be dimensioned on the drawings as 34 <br />inches maximurr. above the Floor, per ICC/ANSI A117.1-2003 secticn <br />60G.3 in toilet rooms, classrooms, labs, and break rooms, per IBC <br />1109.2.3. <br />