Laserfiche WebLink
Accessibility Issues per ICC/ANSI At 17.1-2003-sec next page <br />I. Item 5 from previous letter: the vertical sidewall bar should be provided at a minimum 18 <br />inches long, mounted with bottom of bar located between 39 and 41 inches above the <br />floor, and center line of the bar located between 39 and 41 inches from rear wall. <br />2. Item 8 from previous letter: the toilet paper dispensers should be located 7 inches <br />minimum and 9 inches maximum in front of the water closet, measured to the centerline of <br />the dispensrr-Section 604.7. <br />3. Item 10 from previous letter: the entrance to both toilet rooms from the Narthex requires a <br />wider corridor, 54" minimum width for a latch approach pull side on a door with a closer, <br />per figure (f) in Figure 404.2.3.1. The previous letter referenced 60" minimum width. <br />4. Item 1 I from previous letter: the entrance into the Women's toilet room requires <br />minimum 30-inch width in the path of travel (restricted by the surface mounted paper <br />towel dispensers) -Section 305.3. Submit cut on towel dispensers and dimension them on <br />plan to address the clearance requirements. <br />Upon resubmission of the drawings, your application will be given priority and plan review will begin. <br />All required submittals should be of sufficient detail and contain sufficient information to ensure that <br />the proposed structure will be constructed in compliance with .II adopted codes. Please feel free to <br />call me to discuss at 425-257-8813, or drop by the permit counter at your convenience. <br />Sincerely, <br />5WIIA"WwC 1p 1 WW(.'i'P"WIM('oma.�nI nn ex <br />