6 <br /> Approximate <br /> OUT OF SCOPE ITEMS(CONTINUED) Design Fee <br /> PLANT WATER PROJECT <br /> Plant water system <br /> A feeder from FWPS2 MCC section 7 of 10 to supply the new plant water pump <br /> building MCC <br /> The vertical buss in this section is rated at 300 amps and will have to be changed to <br /> 600 amp. Per phone discussion with Derrick Foeller at AB on 3/19,no need to <br /> change bus. Horiz bus is center located so there are 2 separate 300 amp buses. Can <br /> install up to 225 amp molded case breaker without major modification work <br /> Therefore assume that 225 A feeder to plant water in the lower half of the vertical bus <br /> and a 80 amp approx breaker in the upper half of the vertical bus. <br /> Load to be calculated with the idea of supplying the new Chlorine building load from <br /> the Plant Water Pump MCC(or the FWPS2 MCC.) Will assume feed from the <br /> FWPS2 MCC since it allows the PW feeder breaker to be sized at 225 amps which we <br /> can probably live with. <br /> Remove the feeder from the new plant water pump building to FWPS1 (this will free up <br /> a breaker that can be used as a tie breaker that is Kirk key interlocked). <br /> Conduit from FWPS2 to the new plant water pump building(perhaps utilizing the <br /> same in-slab feed abandoned by the FWPS1 bullet above.) We could possibly <br /> intercept this but it may be easier to just route direct to the PW building. We would <br /> $7,000 <br /> want two conduits,one for PW and one for new Chlor bldg. Will need to core hole out <br /> of building next to MCC 2 to get conduits from MCC 2 outside the building. Probably <br /> add a site elect plan. <br /> Reconfigure the existing pumps controls. Not in original scope This includes a new <br /> remote I/O panel powered from an existing standby power backed 120 V circuit. The <br /> City will provide interconnect serial I/O cable from the I/O panel to an avaialble 1/0 $5,900 <br /> data port in the PLC in FWPS2.Will include testing of the data comm in the contract <br /> docs. Add a detail for I/O terminal block arrangement. <br /> GENERAL <br /> 99%submittal requested on 3/18104 <br /> Original scope did not include a 99%submittal. $1,300 <br /> Update Specification format:Everett front end to CSI and submittal register <br /> Originally was given WSDOT style from City to include in documents. $1,000 <br /> Total Electrical $27,500 <br /> Total Other $12,400 <br /> Total ;39,900 <br /> 30 Page2of2 <br />