t <br />Ltr. R.Clark (130309-044) <br />October 1, 2003 <br />Page 2 <br />c <br />4. All doors that have a latch set or lock set .should be specified to be lever -type <br />operating hardware. Section 1106.3.1 <br />5. The accessible toilets should be shown to have seat heights from 17"-19" above <br />the floor. Section 1106.11.5.2 <br />6. The length, height, diameter, wall clearance S position of the two grab bars at the <br />water closets should be dimensioned on the plans. Section 1106.11.5.3 <br />7. The toilet flushing mechanisms (levers) should be shown opposite of the near <br />wall. Section 1106.11.5.4 <br />Please prepare a response letter showing where each item in this correction letter is <br />addressed on the plan set. <br />Upon resubmission of the drawings, your application will be given priority and plan <br />rcvie%% will recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to <br />ensure chat the proposed structure will be constructed in compliance with all adopted <br />codes. <br />Sincerely, <br />Tony R. Lee <br />Plans Examiner <br />