Laserfiche WebLink
. . . , � � <br /> 14.Provide sections and details for pantry addition. Show all components <br /> including framing and energy code requirement. <br /> See sheet A5.0 ' <br /> 15.Specify existing beam size in basement. Identify location of all point loads on <br /> existing beam. Verify adequacy of beam. <br /> All point loads are carried directly to foundations via new posts. <br /> 16.Specify location of all footings in basement with dimensions. <br /> See sheet A1.0 <br /> 17.Show how existing 2x10 floor joists are supported by all new beams. Provide <br /> sections and/or details as needed. <br /> See framing plans (AF1.1, AF1.2, AF1.3) <br /> � 18.Provide detail(s) for guard at landing on main floor and (if applicable) along <br /> stairs at second floor. <br /> New pony wall is to be built at base of stairs, new guard along stairs at <br /> second floor. See keynotes 1.27 and 1.28 on sheets A1.1 and A1.2. <br /> - 19.Specify handrail requirements per section R311.7.7 IRC (do not �imply <br /> reference code section). <br /> See details 3 and 4 on sheet A8.0. <br /> .- 20.Show all source specific exhaust fans, clothes dryer exhaust and range hood <br /> „ per chapter 15 IRC. <br /> See sheets A1.1 and A1.2 for source specific exhaust fans. <br /> 21.Specify how dwelling meets the requirements for whole house ventilation per <br /> section M1508. Show which option is used and specify size and location of <br /> fresh air inlets (if applicable). <br /> See sheet G1.0 for calculations. <br /> 3�� <br />