S. Fire tlo�v for this project is I,�00 gpni. <br /> 9. Portable Fire Protection - A ponable fire extinguisher with a minimwn U.L. rating of <br /> 2-A:10-13:C shall h. provided within 75 feet of travel on all 800rs of each building <br /> during construction and prior to occupancy. <br /> 10. Pire Alarm S��stem - An approved automatic fire detection system shall be provided as <br /> required by Ciry Ordinance No. 30J_I-07, Chapter 16.76, of the Everett Municipal Code. <br /> Plans for such system shall be submitted to the Fire Marshal for review and approval <br /> prior to installation. Submittal shall include cut sheets of all equipment intended for use. <br /> Appropriate trip lests, witnessed by a Fire Department inspector, shall be perfornted, <br /> along with a certificate of completion, prior to final acceptance of the system. <br /> Pire alarm systems shall be installcd according to NFPA Standard 72. (nstallation oC <br /> fire alarm components, in�luding basic wiring, may not commence befar� plans arc <br /> approved by the Fire Department Plan Revicwer. Fire alarm drawings must be <br /> professionally rendered, in sufficient detail, and must be internally consistent. Riscr <br /> diagrams must match installation plans and load caleulations. Components must be listed <br /> and approved For use together. Changes to plans must include new drawings and <br /> calculations and must be upproved by the Fire Department Plan Revicwer prior to <br /> installation. Pire alarni installation is subject to ficld inspection by a Fire Departmer.t <br /> Inspector. An approved set of plans and the Building Department eleccrical permit must <br /> be present for any installation inspection. <br /> Pire alami systems shall be installed under permit of the City of Cverett l3uilding <br /> DepartmenL Electrical inspections and approval are required prior to calling for <br /> acceptance tests. Fu� pemiit infonnation call (425) 257-85 l0. <br /> The abscnce of working phone lines for thc alarm system will be cause for <br /> postponing 6re Jepartment inspection and testing and shall result in �enial of <br /> occupancy. <br /> I I. Construction and demolition of buildings shall be in compliance with the provisions of <br /> the 2006 International Fire Code, Chanter 14. <br /> I"_'. Permits are required from the Pire Department for remo��al and installation of <br /> underground fuel tanks. <br /> 13. All fire alarm control panels (FACP) and sprinkler valves shall be in heated rooms or <br /> closets with standard man door access. Locations shall be npproved by the Fire Marshal's <br /> Office. <br /> I�1. Gates conslructed on the fire apparatus access road must comply with Appendix D, <br /> paragraph D103.5, of the 200G International �ire Code. <br /> 3 <br />