Plans for any such system shall be submitted to the Building Department for examination and <br /> approval. Such plans shall include plans for the underground mains that will supply ihe sprinkler <br /> systcm. <br /> The type of sprinkler to be installed will be determined by the Building OfficiaL It may be an NFPA <br /> 13, NPPA 13R, or NFPA 13D system depending upon several factors. Sprinkler 9nstallatioo shall <br /> not begin without an approved and stamped sct ot plans from the Building Department. The <br /> Pire Department will also review the plans and shall field inspect the installation based only on <br /> approved plans that must be on site. Changes to plans must be approved by both the Building and <br /> Fire Departments. <br /> Aboveground sprinkler piping shall be hydrostatically tested as established in NFPA Standazd 13. <br /> Underground piping shall be hydrostatically tested and flushed as established in NFPA Standazd 24 <br /> for private firc mains. (Below-Eround ninine must be installed bv Washineton State Patrol <br /> Licensed Undereround Snrinkler line certified "U" installers. For further intormation,contact <br /> thc Statc Firc Marshal's Office at (360) 570-3134 or contact thc E�•erett Firc Department at <br /> (425) 257-8123.) A!l such tests shall be witnessed by a Fire Depariment inspector. Call (425) 257- <br /> 8124 to make an appointment for inspection. <br /> Contractors' materials and test certificates shall be submitted to the Everett rire Department prior ro <br /> issuance of any Ccrtificates of Occupancy. <br /> Call (425) 257-8123 for morc information. <br /> 1 l. Sinele I�amil or Duplex- Singlc family or duplex structures that are required to have a fire sprinkler <br /> system may use a si�tglc domestic water meter(see City of Everett Public Works Standard Drawing <br /> 502C). 1'he size of the service meter shall be calculated by the civil engineer or fire sprinkler designer <br /> wh� i� solel}' responsible for these calculations. Thc City Public Works Department does not review <br /> these colculations and is not the authority having jurisdiction. The fire service side of the system must <br /> hnve a statc-approvcd backllow prcvcntion dcvicc. <br /> l2. Construction and demolition of buildings shall be in compliance with the provisions of the 2003 <br /> Internationnl Pire Code, Chapter 14. <br /> 13. Permits are rcquired from the Fire Department for removal and installation of underground fuel tanks. <br /> 14. Abandoncd tviks sliall be pmnpcd out:uid the fuel properly disposed of prior to removal. No product or <br /> rinsc wnter may be disposed of in such a way that it could entcr the storm drains systan. <br /> l5. All fire alarm control pancls (PACP) and sprinklcr valves shall be in heated rooms or closets with <br /> standard man door access. Locations shall be approved by the'Fire Marshal's Uffice. <br /> 1 G. 1'rush Collection - Dumpsters over 1.5 cubic yards capacity shall be located a minimum of 5 feet from the <br /> building [IPC 304.3.3, 2003 Gdition]. <br /> \���� 1 <br /> s <br />