Laserfiche WebLink
Ltr. B. Murphy <br />April 9, 2007 <br />Page 2 <br />Please include the requirement for radiation dampers at all bathroom, kitchen and <br />laundry room fans in accordance with IBC 716.6.2. <br />Please provide structural calculations and detailing for the footing pads. Include <br />allowable reinforcing requirements. <br />9. Please include the requirement for a concrete -encased electrode (ufer ground) required <br />per NEC 205.50. (Inspected with footings). <br />10. Please provide detailing for all structural hold down hardware straps and straps. <br />11. Please indicate the requirement for hot -dipped zinc -coated galvanized steel, stainless <br />steel, silicon bronze or copper for all fasteners to be used in preservative -treated wood. <br />12. Please provide the detailing necessary to assure compliance with RCW 64.55 <br />(enclosed). Also required will be a stamped statement assuring compliance. <br />Please prepare a response letter showing where each item in this correction letter is addressed <br />on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />reconmience. <br />Alt required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />Steve Miller <br />Associate Engineer <br />DEVI PI.NCKNtSTV MILLER DOIDM-M (3011 W MARINE VIEW DR) <br />�J <br />