MEMORANDUM <br />Page 2 <br />November 25, 1983 <br />Item #3: Agree, will comply. <br />Item #4: Telephones comply. See interior elevation on sheet A10.4 and <br />units #32, sheet A13.4. <br />Item #5: Lever operated lock sets and latches are provided where <br />appropriate. See finish hardware specification, Section 8700, <br />page 34. <br />Item #6: Agree, have complied. See electrical drawings. <br />Item 07: Agree, have complied. See mechanical drawings. <br />Occupancy and Construction Comments <br />Item #1: All cells have concrete floors (noncombustible) carpet is <br />provided in most staff supervised dayrooms and multi -purpose <br />areas except at high security and psychiatric housing areas <br />on Level 4 and 5. Carpet flammability is Class "B" (NFPA <br />flame spread 26-75, which we feel complies with the intent of <br />Table 42-B). Inmates are "forcibly restrained" in the cells <br />and dormitories at night. Carpets have been specified in <br />these areas for acoustical reasons at the request of Snohomish <br />County for environmental concerns. <br />Iter^ 42: Project design complies. The mechanical ventilation systems <br />were desgined for a minimum of 5 CFM outside air per occupant <br />and total air circulation as required to conform to ASIIRAE <br />requirements. (IINTB comment.) <br />Item IQ: The basement parking garage ventilation system is designed for <br />a minimum air exahust of 12,000 CFMs which conforms to the <br />requirements of Sect. 705, UBC. <br />Item #4: All walls on Level S2 exceed 1-hour rating. Doors #S2.02, <br />S204, S210, (S207) and S205P will be required to be 1-hour <br />rated. S2.03 will be changed to 1;-hour rated as required by <br />a later item. (Change order required.) <br />Item #5: All toilet room floors and base are ceramic mosaic tile which <br />complies. See finish schedule. All toilet room walls not <br />provided with tile are provided with epoxy coating at "wet <br />areas." Masonry filler plus epoxy coatings complies as a <br />smooth surface as specified. <br />Item #6: Plan on sheet A9.3 shows 32" width at water closet stool. <br />