My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
4004 RUCKER AVE 2016-01-01 MF Import
>
Address Records
>
RUCKER AVE
>
4004
>
4004 RUCKER AVE 2016-01-01 MF Import
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/5/2017 1:53:13 AM
Creation date
3/9/2017 12:17:51 AM
Metadata
Fields
Template:
Address Document
Street Name
RUCKER AVE
Street Number
4004
Imported From Microfiche
Yes
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
120
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
(�'r <br />11. A fire hydrant is required within 200 driving feet, but not cioser t6an 50 feet, of every <br />structure. Location of the hydrant(s) shell be approved by the Fire Marshal. <br />12. PREMISE IDENITIFICATION AND ALL REQUIRED FIRE DEPARTMENT ACCESS <br />ROADS AND FIRE HYDRANTS SHALL BE IN SERVICE PRIOR TO <br />COMMENCEMENT OF CONSTRUCTION. <br />13. Portable Fire Protection - A portable fire extinguisher with a minimum U.L. rating of <br />2-A:10-B:C shall be provided within 75 feet of travel on all floors of eacn building during <br />construction and prior to occupancy. <br />14. Fire Alarm System - An approved automatic fire detecNon system shall be provided as <br />tequired by Ciry Ordinance No. 1902-92, Chapter 16.76, of the Everett Municipal Code. <br />Plans for such system shall be submitted to the Fire Matshal for review and approval prior to <br />installation. Submittal shall include cut sheets of all equipment intended for use. Appropri8te <br />trip tests, wimessed by a Fire Depaztrnent inspector, shall be performed, along with a <br />certificate of completion, priur to final acceptance of the system. <br />Fire alarm systems shall be installed according to NFPA 3tandard 72. <br />Fire alarm systems shall be installed under permit of the Ciry of Everett Building Depaztrnent. <br />Electrical inspections and approvai are required prior to calling for acceptance tests. Call <br />(425) 257-8810 for permit inform^.tion. <br />15. Fire Suppr�ssion (Sprinkler) System - An approved automatic suppression system shall be <br />provided as required by City Ordinance No. 1902-92, Chapter 16.76, of the Everett Municipai <br />Code. <br />Plans for any such system shall be submitted to the Building Department and the Everett Fire <br />Departrnent for examination and approval. Such plans shall include plans for the underground <br />mains that will supply the sprinkler system. <br />Aboveground sprinkler piping shall be aydrostatically testai as established in NFPA Standard <br />13. Underground piping shall be hydrostatically tested and flushed as escablished in NFPA <br />Standard 24 for private fire mains. All such usu shall be wimessed by a Fire Depariment <br />inspector. Call (425) 257-8123 to make an appoinunent for inspectioa. <br />Contractors' matetials and test certificates shall be submitted to the Everett Fire Depaztment <br />prior to issuance of any Certificates of Occupancy. <br />Call (425) 257-8123 for more information. <br />1G. Fire Safe - Fire safery practices during construction shall be in compliance with Article 87 of <br />the Unifornt Fire Code. <br />17. For fire safery in multi-family projects with communiry laundry facilities, the following is <br />required: <br />
The URL can be used to link to this page
Your browser does not support the video tag.