Laserfiche WebLink
WED 8. <br />The distance between the pump island canopy and the store must be increased to <br />40 feet grr one wall of either building must be one hour construction. Table 5-A. <br />A one hour occupancy separation wall must be provided between the pump island <br />canopy and the store prr two exits not in the same wall conforming to Sec. 1003 <br />must be provided. Sec. 311.2.3.2. <br />Two exits must also be provided per Table 10-A. <br />Please provide calculations per Sec. 2403 for the floor to ceiling glass areas. <br />Provide safety glazing for these areas per Sec. 2406.4. <br />Please indicate insulation R-valves and U-factors. Please provide energy <br />calculations or indicate prescriptive path. <br />Please indicate fixture heights for all toilet room fixtures. <br />An accessible eating area is required. Sec. 1105.4.5. <br />Permanent roof access is required. UMC Sec. 321.8. <br />Please indicate the roof slope. Sec. 1506.1. <br />Please provide interior and exterior lighting power allowance calculations. <br />Please note that canopy lighting is not exempt per footnote 6. Table 15-1. <br />Upon submittal of the drawings, your application will be given priority and plan review <br />will commence. <br />All required submittals shall be of sufficient detail and contain sufficient information to <br />ensure that the proposed structure will be constructed in compliance with all adopted <br />codes. <br />Sincerely, <br />e fey 'McFall <br />Associate Engineer/Building <br />1M jd: OM <br />