Laserfiche WebLink
� � <br /> Construction <br /> C1�Suspended ceiling systems are designed to be level (to within 1/8" over 12") and shall <br /> be attact,ed to structure at the perimeters. The proposed clouds are sloping and <br /> detached from the walls. The manufacturer's listing must be provided which shows the <br /> system has been approved for this proposed configuration. UBC Standard 25-2, <br /> Section 25.210 <br /> BN&H: Armstrong World Industries, the manufacturer of the suspended ACT 8 GWB <br /> ceiling systems as drawn and specified for this project, referred our office to a <br /> structural engineering office ir. Portland, Oregon, for the generation of <br /> engineering calculations and details speci�c to the needs of this project's <br /> installation conditions. The manufacturer provides this avenue of certification <br /> for their product usage in lieu of issuiny generic reports. This addresses the <br /> need to meet code seismic-zone-specific design parameters. Attached are <br /> structural engineering calculations and details generated specifically for the <br /> suspended ceiling conditions used on this project. This engineering ensures <br /> full compliance with UBC Stardard 25-2 and other applicable code references. <br /> The special structural details have been added to the project drawings by <br /> Addendum No. 4, dated June 3, 2003. These engineering calculations will te <br /> submitted to accompany this letter. <br /> r 2�Various suspended ceiling detaiis on sheet A11.0 show horizontaily stacked and/or <br /> \ ,% disconlinuous, cantilevered ceiiing system (such as for a Iight cove or window shade). <br /> The manufacturer's listing must be provided which shows the system has been <br /> approved for these proposed confiqurations. <br /> BNBH: Piease refer to the repiy for Item 1, above. <br /> ! 3. Requirements for lateral bracing and compression struts for the suspended ceilings <br /> should be provided on the plans. UBC Standard 25-2, Section 25.212.3 <br /> BN&H: Please refer to the reply for Item 1, above, for the various special ceiling <br /> conditions. Our standard office detail addressing this matter for all non-special <br /> suspended ACT ceilings, has been added to the drawings by Addendum No. 4, <br /> dated June 3, 2003, as drawing SK-A11.1-7, Detail 7 Typ. Ceiling Suspension <br /> Bracing, Ail Conditions. <br /> 4. All rated walis shouid have their listing shown on the plans (all partitions must be <br /> minimum one-hour rated unless they are within an office or store space). Sections <br /> 601.1, 601.5.2.1 8 1703.1 <br /> BN&H: Addendum No. 4, dated June 3, 2003, amended drawing sheet A8.0 Wall <br /> Types to add or revise UL listings for Wall Types N, N1, N4, N5, N6, P, P1, & <br /> Z3 with existing CMU; and to delete Wall Type N2. <br /> 5. Note 12 on sheet A8.0 sheuld be revised to require fire-retardant treated wood, or a <br /> non-combustible blocking. Section 602.1. <br /> BN&H: Addendum No. 2, dated May 20, 2003, made that change. <br /> 6. A d��iail should be added for required backinc� in stair and shaft walls showing a non- <br /> con�bustible material. <br /> BN&H: Note 12 on sheet A8.0, as revised by Addendum No. 2, dated May20, 2003, <br /> appiies to all blocking conditions. All stairs and all handrails and guardrails are <br /> z � <br />