Laserfiche WebLink
f <br />Plan Check Review Nos <br />October 12, 1998 <br />Page 8 of 9 <br />B59674,B59674, B59676 <br />)width <br />Side approach to the latch side of a door which must be pulled open requires a minimum clear <br />of 48 inches perpendicular to the door, and a minimum clearance of 24 inches parallel <br />and in front of the door on the latch side. Door #10 of the Interior and End unit plans and N5 <br />of the Interior unit plan should be revised. Section 1006.10.3, Item N8 <br />For a hinge side approach, where a door must be pushed to be opened, an unobstructed floor <br />space, measured from the latch side, should be shown to extend across the width of the <br />doorway and beyond the hinge side of the door for a total width of not less than 54 inches, <br />and at least 48 inches perpendicular to the doorway. Doors #4 & #6 in the Interior unit -,,tans <br />should be revised. Section 1006.10.3, Item N5 <br />The kitchen in the Type A units should have a 30" x 24" counter with a maximum height of <br />34". The space beneath the counter should be at least 29" high, 30" wide, and 19"-25" deep. <br />Cabinets may be installed beneath the counter space, provided that the cabinetry or shelving <br />is not permanent , and is easily removable. Sections 1106.2.3, 1106.12.2 & 1106.27.2.2 <br />A 30" x 48" cleat floor space should be provided at one shower or bathtub in the Type B <br />dwelling units. The 48" dimension should be alongside the shower or tub. Lavatories may <br />encroach on the clear floor space if they are fully accessible or adaptable per Section 1106.11.7. <br />Sections 1106.27 exc. 12, 1106.11.9.1, & 1106.11.10.2 <br />(J17. In each Type B unit, a clear floor space should be provided at one toilet per Section 1106.11.5.1. <br />This requires a 42" lateral clearance from the centerline of the water closet to the nearest <br />obstruction on one side, and an 18" clearance on the opposite side. An accessible or adaptable <br />lavatory may be located in the clear floor space if the edge of the lavatory is at least 15" from the <br />centerline of the water closet. Section 1106.11.5.1 <br />Ene <br />1. apor retarders having a perm ratio of one or less should be shown installed on the warm side at <br />all walls separating conditioned space from unconditioned space. Note that face stapling s <br />C2. <br />required with faced batt insulation. Section 502.1.6 <br />.h tails A & B/A-5.0 show the roof insulation in the truss system, whereas Sections I & 2/A-8.0 <br />ow the insulation above the ceiling. The intended method should be clarified. Section <br />C3)02.1.6.5 <br />-ecessed lighting fixtures, if used, should be IC rated. Section 502.4.4 <br />