Laserfiche WebLink
J 2410 38th Street <br /> December 27, 1990 <br /> Page three of three <br /> �'" <br /> �--I3. The design oP masonry walls with an h'/t ratio larger than 30 should <br /> c_-' comply with the slender wall requirements of Section 2411. <br /> f/14. Spacing of bolts should comply with Section 25.1717 UBC Standards. <br /> Show bolt sizes and spacing on drawings. <br /> � 1�. CMU lintels over openings of more than 4 feet must be designed and <br /> detailed. <br /> f� 16, Railing details 10, 11, 13, & 15 of Sheet :,8 should comply with UBC <br /> 1711. <br /> " 17. Slopes shown on roof plan should be corrected to show 1/4" per foot. <br /> 18. Reinforcement and crack control must be indicated in the plans for the <br /> slabs on grade. <br /> Ir. order for the processing of your application to continue, it wi11 be <br /> necessary to provide the Building Department with two complete new sets of <br /> drawings reflecting the corrections requested. <br /> Upon resubmittal of the drawings, your application will be given priority and <br /> plan review will recommence. <br /> All of the above information shall be of sufficient detail and contain <br /> sufficient information to ensure that the proposed structure will be <br /> constructed in compliance with the City Building Code. <br /> Sections shall be applicable to plan submitted. <br /> Sincerely, <br />� Steve Miller <br /> Associate Engineer <br /> SM:gab/49-6 <br />