' ' �IRE/LIFE SAFETY REPORT S41915 — Page 4 <br /> ' PROVIDENCE EVERETT MEDICAL CENTER February 05, 2008 I <br /> NEW TOWER EXPANSION <br /> 1 b. Nonbearing -- Non-rated I <br /> ' 2. STRUCTURAL FRAME — 3-HOUR, 2-HOUR WHERE <br /> SUPPORTING ROOF ONLY <br /> � 3. SHAFTS — 2-HOUR <br /> ' 4. ROOF — 1-HOUR <br /> ' 5. FLOOR — 2-HOUR <br /> � C. Fire Resistive Separations <br /> 1. Corridors —Allowed to be non-rated. biust be constructed as <br /> � smoke partitions per IBC 710. <br /> 2. Exit Passageways — 2-hour fire barrier. <br /> ' 3. Elevator machine rooms — 2-hour fire barrier. <br /> ' 4. Fire pump room — 1-hour fire barrier <br /> 5. Horizontal Exit — 2-hour fire barrier <br /> ' D. Separation from Existing Hospital, MOB and New Open Parking <br /> Garage <br /> ' 1. Per the available existing drawings, the existing hospital building <br /> , was constructed of Type 1 construction per the 1979 Uniform <br /> Building Code and the existing MOB was constructed of Type II <br /> FI2 construction per the 1985 Uniform Building Code. <br /> � The existirig hospital has a construction type equivalent to Type <br /> I-A construction per the IBC. The MOB has a construction type <br /> ' equivalent to Type I-Q per the IBC. Based on the height and <br /> area of the existing hospital the current code only requires it to <br /> be of Type I-B construction. As all three buildings are allowed <br /> ' to be of Type I-B construction and the area for Type I-B <br /> construction is unlimited for all buildings involved, the new <br /> Tower will be considered an addition to the existing buildings <br /> ' and no Fire Wall separations are required. <br /> � <br />