Laserfiche WebLink
M <br /> r <br /> Mr. Jeffrey S. Skutley <br /> Plan Check No. B45010 through B45027 <br /> December 12, 1994 <br /> Page 4 of 4 <br /> 28. A landing is required on each side of doors not more than 8"below the floor level ('h"at <br /> accessible units). Section 3304(i)). <br /> 29. Water heaters and furnaces within garages must be raised 18"min. above the floor and must <br /> be protected from impact. UMC Section 508. <br /> 30. Provide fan sizes for kitchens, laundries, baths and whole house fans. Provide outdoor air. <br /> Vent dryers and exhaust fans to exterior. <br /> 31. The individual unit plans are very confusing. Please assign a number or letter to each typical <br /> unit plan and indicate on the site plan which typical units make up each floor of each building. <br /> Call out options on site plan so that an inspector will know which plan options will apply to <br /> which buildings. <br /> Indicate stair framing on central stairs buildings P & Q. <br /> Call out wall sections on typical floor plans. <br /> In order for the processing of your application to continue, it will be m.cessary to provide the <br /> Building Division with two complete new sets of drawings reflecting the corrections requested. <br /> Upon submittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure that <br /> the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely <br /> cFall <br /> Associate Engineer/Building <br /> JSM:j c I/ein"wdrkc nrs.doc2.5 <br />