Laserfiche WebLink
7. Update all code references to the 2012 International Residential Code (IRC) and the <br /> 2012 Washington State Energy Code (WSEC). <br /> 8. Provide smoke alarms per Section R314 IRC. Show on plans. <br /> 9. Provide carbon monoxide alarms per R315 IRC. Show on plans. <br /> 10.The plans show an HDU8 hold down at a new 4x4 post at the front porch. There is a <br /> brick guardrail at this location. Please clarify. <br /> 11. Provide lateral analysis prepared by a licensed Washington structural engineer. <br /> 12. Use a different symbol to show existing walls and new walls. <br /> 13. Below grade walls are required to be insulated to minimum R-21 on the interior. Show <br /> furred walls on plan view and provide section/detail for below grade walls. <br /> Please prepare a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review will <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 425-257-8976 <br /> Email: iheilman(Oci.everett.wa.us <br /> c•�lrnmmnn�r�Arfra��7Haf�,,,a„�a�nri�m_nnz��in�rr�„.�e.,o�,�„� �v <br />