Laserfiche WebLink
r � <br /> 6. The plans should show the locations of smoke detectors. The smoke detectors should <br /> be hard-wired, with battery back-up and interconnected within each dwelling unit. IFC <br /> Section 1103.8 <br /> 7. The plans should show the location of the carbon monoxide detector within each unit. <br /> IFC Section 1103.9 <br /> 8. Each toilet room that does not have an operable window to the exterior should be shown <br /> with a minimum 50 cfm mechanical exhaust fan. The fan should be shown not to <br /> penetrate a fire-resistive ceiling without required ceiling radiation dampers, shafts or <br /> alternate approvals. IPMC Section 403.2 <br /> 9. Each kitchen that does not have an operable window to the exterior should be shown <br /> with a minimum 100 cfm mechanical exhaust fan. The fan should be shown not to <br /> penetrate a fire-resistive ceiling without required ceiling radiation dampers, shafts or <br /> alternate approvals. IPMC Sections 403.1 &403.3 <br /> 10. Exposed stud cavities separating conditioned space from non-conditioned space should <br /> be filled with insulation. The R-value of the insulation should be shown on the plans <br /> (Minimum of R-3.0 per inch). WSEC Section C101.4.3 <br /> Please provide a response letter, which shows where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmission of the drawings, your application will be given priority and plan <br /> review will begin. <br /> All required submittals must be of sufficient detail and contain sufficient information to <br /> ensure that the proposed structure will be constructed in compliance with all adopted <br /> codes. <br /> Sincerely, <br /> �y <br /> Tony Lee <br /> Building Official <br />