Laserfiche WebLink
• Since this is not a new tank, a 10 day instead of a 14 day hydration period was applied <br /> before starting the measurement test. <br /> • The level decline was evaluated for all three time classes in the standard (96, 48, and 24 <br /> hours) plus a longer interval of 6 days. Leakage remained relatively constant across the time <br /> intervals. <br /> The Design-Builder shall conduct a leak testing based on the same methodology at the completion of <br /> construction.The measured rate of leakage shall be no worse than the existing leakage rate <br /> measured by the City prior to the Project. If the leakage is measured to be greater,the Design- <br /> Builder shall make necessary improvements such that the leakage is less than or equal to the <br /> existing leakage rate. <br /> 4.6.5 East Clearwell Concrete Floor Slab Spalling Repair <br /> Design-Builder shall repair all interior floor spalling of concrete slab that is in excess of 1/8-inch <br /> deep. <br /> The allowance amount for spalling repair is $36,969.00 for 9,000 square feet(estimated total for <br /> East Clearwell), which is a unit price of$4.1077 square foot of spalling repair. If Design-Builder <br /> repairs less than 9,000 square feet,then a deductive Change Order will be issued for the allowance <br /> amount not spent, calculated based on the unit price and the difference between 9,000 square feet <br /> and the amount of repair actually completed. If Design-Builder repairs more than 9,000 square feet, <br /> then a Change Order will be issued to increase the Contract Price, calculated based on the unit price <br /> and the amount of repair completed in excess of 9,000 square feet. <br /> Assume the average depth of spall repair is 1/2-inch. Provide vertical edges of repair zone (no <br /> feathered edges)to existing concrete. Perform repairs in accordance to the guidelines of ACI 546R <br /> "Concrete Repair Guide." <br /> 4.7 East Clearwell Cleaning and Disinfection <br /> 4.7.1 General <br /> Before refilling completed facilities, including the East Clearwell and pipelines, Design-Builder shall <br /> clean the East Clearwell and pipelines in accordance with applicable standards and procedures, <br /> including but not limited to: WAC 246-290-451, WSDOH, and ANSI/AWWA Standards C652 (Method <br /> 3) and C651, and coordinate disinfection with the City. All materials used for cleaning and <br /> disinfection of potable water tank and system interiors shall conform to the applicable requirements <br /> of ANSI/NSF 60 and 61. <br /> 4.7.2 East Clearwell <br /> Immediately prior to disinfection, Design-Builder shall remove all temporary structures and debris, <br /> and wash all interior surfaces with clean water using a high-pressure water device.All water, dirt, and <br /> foreign material accumulated in this cleaning process shall be removed from the East Clearwell. <br /> Following cleaning, Design-Builder shall arrange for Owner's Representative to inspect and verify that <br /> cleaning requirements have been met. <br /> Upon the City's acceptance of Design-Builder's cleaning process,the City will conduct refill and <br /> disinfection operations. After completion of East Clearwell disinfection, City will conduct testing <br /> activities in accordance with WDOH requirements to confirm absence of coliform organisms and <br /> City of Everett September 13,2017 <br /> Water Filtration Plant Clearwell Roof Replacement DB Project Supplementary Conditions Page 14 <br />