Laserfiche WebLink
• 0 . <br /> d. Previous comment: The drawings should indicate specific signage at the main <br /> entrance door and the exit doors to indicate that these doors will be open during <br /> business hours, per IBC section 1010.1.9.3, item 2.2. <br /> 2. Please show the following in the basement: <br /> a. Previous comment: Emergency lighting should be shown on the drawings, per <br /> IBC section 1006.1, at the interior and exterior side of the door. <br /> Construction <br /> 1. Previous comment: please verify that the hardware on the toilet room doors and stair <br /> are levers, without tight grasping, per IBC section 1010.1.9.1. <br /> 2. A commercial kitchen plumbing permit application is required-per <br /> https://everettwa.gov/DocumentCenter/Home/View/111 <br /> Accessibility <br /> 1. The alteration includes an area of primary function, which requires access from the <br /> tasting room to the two toilet rooms in the office, per IBC section 2902.2. <br /> a. The cost of altering an accessible toilet room does not have to exceed 20% of <br /> the cost of the alterations to the primary function area, per IEBC section 410.7 <br /> exception 1. <br /> b. We discussed the possibility of enlarging both toilet rooms by removing the <br /> alcove, and relocating the entrance doors to the north wall, for improved <br /> accessibility. The method of improving accessibility is entirely up to you. <br /> 2. Previous comment: The sales and service counter should be shown in section and <br /> elevation to meet accessibility requirements of ICC-A117.1-2009 Chapters 9 for service <br /> counters and section 309 for reach ranges. The plan and section show 42 inches, but at <br /> least a 36 inch portion should be no higher than 36 inches, per ICC-A117.1-2009 section <br /> 904.3.1. <br /> Energy <br /> 1. Please indicate the removal of the drywall and studs on the walls that are going to be <br /> exposed on the plans. Is this just in the Port Gardner Bay area or throughout the first <br /> floor? <br /> a. Please indicate that the basement is not heated on the drawings. <br /> b. The first floor has to be insulated with R-30 insulation to prevent heat loss to the <br /> basement, per WSEC Table C402.1.3. Please show this in section. <br /> 2. Previous comment: Please indicate the existing or new ceilings on both levels of the <br /> building section, and a reflected ceiling plan for each floor indicating new or existing <br /> lighting._If you are changing more than 50% of the light fixtures in a space, the <br /> following is required on the drawings or as a supplemental report, per WSEC C503.6. <br /> a. Where more than 50% of the lighting fixtures are added or replaced in any <br /> room, please include actual code section language on the building drawings for <br /> interior lighting controls, sensors, and all other methods of compliance covered <br /> in electrical power and lighting systems per WSEC sections C405 and C503.6. <br /> b. Where more than 50% of the lighting fixtures are added or replaced in any room <br /> please include a calculated lighting summary from the forms available on <br /> NEEC.NET to verify compliance for the interior lighting power allowances per <br /> WSEC table C405.2 (1). <br /> Mechanical Permit application (deferred) <br /> CITY OF EVERETT PERMIT SERVICES 3200 CEDAR ST, EVERETT, WA 98201 425-257-8810 <br /> website: www.everettwa.gov/permit Page 2�/r� email. mhaley@everettwa.gov <br />