4. Door hardware at the egress doors, entrance doors, and the office use doors should be <br /> shown to be accessible on the door schedule, for both new and existing doors, per IEBC <br /> section 410.6. <br /> 5. The pull-side dimension of the new east door from the break room should be shown to <br /> be 18 inches, per ICC-A117.1-2009 Figure 404.2.3.2(a). <br /> 6. Please reference dimensioning details of sheet A6.02 on sheet A6.01 for the interior <br /> toilet room elevations. <br /> Energy <br /> 1. Alterations which replace more than 50% of the luminaires have to comply with lighting <br /> controls, per WSEC C503.6. <br /> a. Please include both the interior and the exterior lighting in the lighting summary <br /> and analysis using the LIGHT-SUM form, per WSEC table C405.5.2 (1). This <br /> WSEC form should be submitted as part of the tenant improvement.\ <br /> b. Please include actual code section language on the drawings for interior and <br /> exterior lighting controls, sensors, and all other methods of compliance covered <br /> in electrical power and lighting systems per WSEC section C405. <br /> 2. Please identify if the S-2 occupancy is semi-heated, per WSEC section C402.1.1.1, or low <br /> energy path, which requires documentation on the plans for the intent for use and <br /> heating of the space per one of the four options summarized in WSEC section C402.1.1. <br /> 3. A change to the space conditioning of the warehouse to semi-heated or to non- <br /> conditioned will require replacement and modification of existing structure and <br /> fenestration of the office and mezzanine structure, per IEBC C503.2. <br /> a. For the change of warehouse occupancy to S-2 vehicular use, please indicate the <br /> prescriptive method of building envelope compliance for the offices first floor and <br /> mezzanine, the existing building within the building, to include detailed R-Values <br /> of existing or modified interior and exterior walls, roof-ceiling cavities, man- <br /> doors and garage doors, per WSEC section C402.1. <br /> b. The U-value requirements for the interior windows and doors on the <br /> office/mezzanine should also be shown to be in compliance with a non- <br /> conditioned space on the exterior. Please indicate the U values of all fenestration <br /> to meet energy code requirements, to include man and rolling doors, per WSEC <br /> C402.1.4 and C402.4. <br /> 4. Where a change in space conditioning is triggering new work, compliance with the <br /> building thermal envelope requirements should be shown in section and summarized on <br /> the drawings, per WSEC section C503.1. Please indicate the method of building envelope <br /> compliance by completing a total UA alternative worksheet, or provide a completed <br /> prescriptive worksheet to include detailed R-Values of new exterior walls, roof-ceiling <br /> details, slab on grade and foundation details, per WSEC section C402.1. <br /> 5. All compliance forms referenced are available on neec.net. <br /> Mechanical <br /> 1. Deferred plan review will still require neec.net mechanical summary compliance forms, <br /> and equipment catalog cuts. <br /> . . . _ . t � <br /> CITY OF EVERETT 3200 Cedar Street Everett, WA 98201 (425) 257 8813 Page 3/� ,� <br />