Laserfiche WebLink
Psychrometrics - Zone Semi Heated � <br /> Calculation 1�'Ionth: .luly Calculation Hour: 4:00 p.m. <br /> Air Conditions Loads(Btu/h) <br /> Airflow Humidity Ratio <br /> (CFni Dry Bulb Wet Bulb <br /> � Temperature Temperature ��bs of moisture/ Total Sensible Latent <br /> lb of dry air) <br /> Outside Air 6,030 81'F 66.13°F 0.0103] 68,500 39,000 29,�00 <br /> Return Air at Uiffusers 2�t,600 85°F 70J2°F 0.01296 <br /> Return Duct Leakage (0%)0 <br /> Return Duct'Cemperature Gain +0°F 0 0 0 <br /> Return Air at Aparatus 24,600 85°F 70.72°F 0.01296 <br /> Mixed Air 3QG00 84.21°F 69.74°F O.f)]244 <br /> Coil Dew Yoint 26,000 49.59°F 4959°F 0.00756 <br /> Coil 13ypass Air (1 S%,)4,600 8421°F 69.74°F 0.01244 <br /> Coil Leaving Air 3�,600 54.78°F 53.07°F 0.00829 <br /> System Load 848,000 974,000 -126,000 <br /> Reheat +0°F <br /> Humidification 0.00500 <br /> Fan(Draw Through,2 HP) +0.]S°F 5,090 5,090 0 <br /> Motor(In Airstream,70% Efficient) +0.07"F 2,180 2,180 0 <br /> Supply Uuct Leakage (0%r)0 <br /> Supply Duct Temperature Gain +0°F 0 0 0 <br /> Supply Air at Diffusers 30,600 55°F 55°F 0.01329 <br /> Room Load -0.f10033 960,000 1,O10,000 -48,600 <br /> Final Room Conditions 85°F 70.72°F 0.01296 <br /> .," <br /> � ��� . <br /> ,�I. , <br />