Laserfiche WebLink
� � .• <br /> • 2. IPMC 702.1 'Means of Egress' requirements are not met on the first floor retail, �actorv, and office occupancies <br /> (6000 square feet). <br /> a. The second required exit through the basement does not have an illuminated exit sign or emergency <br /> lighting. <br /> b. Since the first floor is not protected with fire suppression, a direct exit to the public way is required through <br /> the basement. <br /> 3. IPMC 702.1 'Means of Egress' requirements are not met in the basement. The plans are not clear as to the <br /> occupancies in the current submittal (approx. 16,000 square feet). <br /> a. Required exits do not have illuminated exit signs or emergency lighting. <br /> b. Required exits have doors which can be locked to prevent egress. <br /> Under the retroactive requirements of the 2012 International Fire Code, Chapter 11,the owner was informed that the <br /> building located at 3231 Broadway does not meet minimum egress requirements, per the 6/27/14 letter attached. <br /> • An incomplete building permit application was submitted on 10/30/14, per the second attachment. <br /> � <br /> l�'�Y4t1b-0{17 3Z31 2nd <br /> Fire Department.., notifitatian.pdf <br /> BGi�. <br /> MC9 <br /> Meg Haley, FtA � p�aw rz.evCew Rrch�tcct � peYrui.t servCccs,c�t�o f EvcYett � s2oo cedav st � Everctt,Wi198201 <br /> 425-257-8813 ( mhaleyCe�ever�ttwa.4ov � h�p://www.cC.everett.wa.us/d�fault.aspx?iD=zi�o <br /> 2 , <br />