Laserfiche WebLink
F-1 <br /> t <br /> _ ___, <br /> TAHOMA <br /> DESIGN GROUP <br /> July 17,2017 <br /> Mr. Tony Lee, Building Official <br /> City of Everett <br /> Engineering Public Services Department <br /> 3200 Cedar Street <br /> Everett, WA 98201 <br /> Project: Riverside Business Park Shell Building,TDG No. 2160819.01, Task 03 <br /> Subject: Response to Comments dated June 14, 2017 <br /> Plan Check No: B1704-042 <br /> Dear Mr. Lee: <br /> This letter is in response to your comments dated June 14, 2017 regarding the above referenced project. <br /> The comments are included below (verbatim) for your reference. Our responses are shown in bold after <br /> each comment. <br /> General <br /> Floor footnote #7 should be revised to the 2015 IBC. The Assemblies Occupancies(even if <br /> Accessory) should be accounted for in the Building Information sections. These would include <br /> conference rooms and break rooms with a floor area greater than 750 square feet. Section <br /> 508.2.1 <br /> Response: Footnote#7 has been revised to refer to IBC 2015,Section 508.2.1. <br /> Accessory occupancies shall be individually classified in accordance with Section 302.1 <br /> (see Sheet A1.03). <br /> tom• Exiting through a storage room (room 302) is not permitted per Section 1016.2, Item 5. <br /> Response: Room 302 has been changed to Hallway 302. <br /> Because there is a folding partition between mezzanine conference rooms 210&211,the <br /> Assembly rooms have a combined occupant load greater than 50 when the partition is open. As <br /> such,the following comments apply: <br /> Response: Noted. <br /> 535 DOCK STREET P: 253-284-9680 tahomadesigngroup.com <br /> SUITE 211 F: 253-284-9681 <br /> TACOMA,WA 98402 i/ <br />