Laserfiche WebLink
Seatronics,Inc. Boeing 40-37 Section 1 <br /> Job: 111025 Fire Alarm System Submittal Manual Page 2 <br /> SYSTEM SEQUENCE OF OPERATION <br /> 1. ALARM CONDITIONS: <br /> 1.1 ACTIVATION OF ANY SPOT TYPE SMOKE DETECTOR, MANUAL PULL STATION OR WATER <br /> FLOW SHALL: <br /> a. CAUSE THE ALARM INDICATOR LAMP ON THE FACP TO ILLUMINATE. <br /> b. CAUSE THE INTERNAL SOUNDER DEVICE IN THE FACP TO ACTIVATE. <br /> c. DISPLAY PROPER MESSAGE ON FACP LCD DISPLAY WITH ALARM POINT LOCATION <br /> INFORMATION. <br /> d. DISPLAY ALARM POINT LOCATION ON THE REMOTE ANNUNCIATORS. <br /> e. CAUSE BUILDING FIRE ALARM STROBES AND HORN/STROBES TO ACTIVATE. <br /> f. ACTIVATE THE FACP DIGITAL DIALERlCOMMUNICATOR AND TRANSMIT AN ALARM <br /> SIGNAL TO THE TYCO CENTRAL STATION MONITORING COMPANY. <br /> 2. SUPERVISORY CONDITIONS: <br /> 2.1 ACT[VATION OF ANY FIRE SPRINKLER TAMPERS SHALL: <br /> a. CAUSE THE SUPERVISORY INDICATOR LAMP ON FACP TO ILLUMINATE. <br /> ' b. CAUSE THE INTERNAL SOUNDER DEVICE IN THE FACP TO ACTIVATE. <br /> c. DISPLAY PROPER MESSAGE ON FACP LCD DISPLAY WITH SUPERVISORY POINT <br /> LOCATION INFORMATION. <br /> d. ACTIVATE THE FACP DIGITAL DIALER/COMMUNICATOR AND TRANSMITA <br /> SUPERVISORY SIGNAL TO THE TYCO CENTRAL STATfON MONITORING COMPANY. <br /> Seatronics, Inc. PO BOX 1138 Auburn, WA 98001 253-939-6060 <br />