Seatronics,Inc. Boeing 40-37 Section 1 <br /> Job: 111025 Fire Alarm System Submiftal Manual Page 3 : <br /> 3. ELEVATORS <br /> 3. ALARM CONDITIONS— ELEVATOR LOBBIES: <br /> 3.1 ACTIVATION OF SMOKE DETECTOR(S)ON FLOOR 2, 3, 4, 5, 6, PENTHOUSE LOBBY SHALL <br /> CAUSE THE FOLLOWING TO OCCUR: <br /> A. ILLUMINATE THE RED "ALARM" INDICATOR ON THE FAP. <br /> B. DISPLAY MESSAGE ON THE CONTROL PANEL LCD DISPLAY INDICATING LOCATION <br /> INFORMATION FOR THE DEVICE THAT WAS ACTIVATED. <br /> C. ACTIVATE ALARM BELL UNIT(S) IN ELEVATOR LOBBIES. <br /> D. TRANSMIT AN "ALARM"SIGNAL TO THE REMOTE MONITORING STATION. <br /> E. RECALL ELEVATOR TO PRIMARY FLOOR(FLOOR 1). <br /> 3.2 ACTIVATION OF SMOKE DETECTOR ON THE 1ST FLOOR ELEVATOR LOBBY SHALL CAUSE <br /> THE FOLLOWING TO OCCUR: <br /> A. ILLUMINATE THE RED"ALARM" INDICATOR ON THE FAP. <br /> B. DISPLAY MESSAGE ON THE CONTROL PANEL LCD DISPLAY INDICATbNG LOCATION <br /> INFORMATION FOR THE DEVICE THAT WAS ACTIVATED. <br /> C. ACTtVATE ALARM BELL UNIT(S) IN ELEVATOR LOBBIES. <br /> D. TRANSMIT AN "ALARM"SIGNAL TO THE REMOTE MONITORING STATION. <br /> E. RECALL ELEVATOR TO THE ALTERNATE FLOOR(FLOOR 2). <br /> 4. ALARM CONDITIONS—MACHINE ROOM <br /> 4.1 ACTIVATION OF A SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM SHALL CAUSE <br /> THE FOLLOWING TO OCCUR: <br /> A. ILLUMINATE THE RED"ALARM" INDICATOR ON THE ELEVATOR FAP. <br /> B. DISPLAY MESSAGE ON THE CONTROL PANEL LCD DISPLAY INDICATING LOCATION <br /> INFORMATION FOR THE DEVICE THAT WAS ACTIVATED. <br /> C. ACTIVATE ALARM BELL UNIT(S) IN ELEVATOR LOBBIES. <br /> D. TRANSMIT AN "ALARM"SIGNAL TO THE REMOTE MONITORING STATION. <br /> E. RECALL ELEVATOR TO THE PRIMARY FLOOR(FLOOR 1) <br /> F. ACTIVATE ELEVATOR FLASHING FIRE—HAT CONTROL. <br /> 4.2 ACTIVATION OF A HEAT DETECTOR IN THE ELEVATOR MACHINE ROOM SHALL CAUSE <br /> THE FOLLOWING TO OCCUR: <br /> A. ILLUMINATE THE RED "ALARM" INDICATOR ON THE ELEVATOR FAP. <br /> B. DISPLAY MESSAGE ON THE CONTROL PANEL LCD DISPLAY INDICATING LOCATION <br /> INFORMATION FOR THE DEVICE THAT WAS ACTIVATED. <br /> C. ACTIVATE ALARM BELL UNIT(S) IN ELEVATOR LOBBIES. <br /> D. TRANSMIT AN "ALARM"SIGNAL TO THE REMOTE MONITORING STATION. <br /> E. ACTIVATE ELEVATOR POWER SHUNT TRIP BREAKER(SHUTDOWN POWER TO <br /> ELEVATOR). <br /> Seatronics, Inc. PO BOX 1138 Aubum, WA 98001 253-939-6060 <br />