Laserfiche WebLink
cv <br /> Z\ 4, <br /> W ,,iC <br /> EXHAUST AND RETURN GRILLES U LI <br /> MARK EG1 EG2 EG3 EG4 EG5 EG6 EG7 EG8 EG9 EG10 EG11 EG12 EG13 EG14 EG15 EG16 EG17 EG18 EG19 EG20 EG21 EG22 <br /> Z *"'"' <br /> TYPE DESCRIPTION LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED EGG CRATE LOUVERED LOUVERED LOUVERED EGG CRATE EGG CRATE (13 <br /> MATERIAL STEEL STEEL STEEL STEEL ALUM ALUM ALUM ALUM STEEL STEEL STEEL STEEL STEEL STAINLESS ST STAINLESS ST STAINLESS ST ALUM ALUM STEEL STEEL STEEL STEELw ........, <br /> BORDER TYPE [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] <br /> CAPACITY NOMINAL FACE: IN 14x14 24x12 24x12 24x24 14x14 16x16 24x12 24x24 20x14 26x18 38x20 38x26 50x26 20x12 24x24 38x14 24x24 48x24 1 1 x 1 1 16x16 48x18 62x26 0 ,c-a3 <br /> NOMINAL DUCT SIZE 12x12 22x10 22x10 22x22 12x12 14x14 22x10 22x22 18x12 24x16 36x18 36x24 48x24 18x10 22x22 36x12 22x22 46x22 9x9 14x14 46x16 60x24 <br /> BRANCH DUCT SIZE 10 10 12 22x12 10 12 14 18x12 12 18x12 24x14 26x18 30x18 18x10 18x16 16x12 20x16 24x16 8 14x5 24x14 30x14 <br /> MAX FLOW: CFM 350 350 700 1,600 300 500 800 1,250 675 1,250 2,300 3,000 4,600 350 1,500 1,200 2,250 3,700 190 280 2,200 3,100 0 r0 <br /> MAX SP: IN WG 0.05 0.05 0.05 0.05 0.05 0.05 0.07 0.05 0.05 0.05 0.07 0.07 0.07 0.05 0.05 0.05 0.08 0.07 0.08 0.02 0.04 0.05 i C 44-) <br /> MAX CORE VEL: FPM 400 260 510 510 350 410 585 400 500 510 550 530 540 315 485 440 720 555 435 230 470 525 • , <br /> MAX NC [2] 11 11 15 18 11 11 20 15 13 15 22 22 22 11 17 15 22 25 17 10 14 14 <br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS <br /> Of LLJ <br /> MODEL 350RL 350RL 350RL 350RL 350FL 350FL 350FL 350FL 350 RL 350 RL 350 RL 350RS 35ORS 350RL-SS 350RL-SS 350RL-SS 50F 350RL 3300RL 33R 50F 50F <br /> NOTES [3, 4] [3, 4] [3, 4] [3, 4] [3, 4] [3, 4] [3, 4] [3, 4] [4] [4] [4] [4] [3, 4] [3, 4] [3, 4] [3, 4] [3, 4] [3, 4] [3, 4, 5] [3, 4, 6] [3, 4] [3, 4] <br /> NOTES: <br /> 1. PROVIDE GRILLES WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT CEILING SYSTEMS, REFER TO ARCHITECTURAL DRAWINGS. 4 <br /> 2. NC BASED ON OCTAVE BANDS 2 - 7 SOUND POWER LEVELS MINUS A ROOM ABSORPTION OF 10 DB, MEASURED PER ASHRAE 70-91. <br /> 3. PROVIDE ATTACHED PLENUM. SEE DETAIL . <br /> 4. DUCT SIZES AS SCHEDULED UNLESS NOTED OTHERWISE ON PLANS. <br /> 5. MEDIUM SECURITY GRILLE. EVERETT,WASHINGTON <br /> 6. HEAVY DUTY CONSTRUCTION. <br /> .GUNS(I. <br /> SUPPLY GRILLES <br /> MARK SG1 SG2 SG3 SG4 SG5 SG6 SG7 SG8 SG9 SG10 SG11 SG12 FG1 FG2 N LG r S <br /> 2 <br /> TYPE DESCRIPTION LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED LOUVERED FLOOR GR FLOOR GR -yt) tiC <br /> MATERIAL STEEL STEEL STEEL STEEL STEEL STEEL STEEL STEEL STEEL STEEL STEEL STEEL STEEL STEEL <br /> BORDER TYPE [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] h'/TEC <br /> CAPACITY NOMINAL FACE: IN 12x8 12x12 18x12 24x12 36x12 30x18 42x18 36x24 30x24 18x36 36x36 22x22 3' WIDE 3.5" WIDE <br /> DUCT CONN: IN [3] 8x8 12x8 12x12 14x12 20x12 24x14 24x18 36x24 30x24 18x36 36x36 20x12 48X3 48X3.5 Architecture/Planning/Interior Design <br /> Portland Seattle Los Angeles Washington DC <br /> MAX FLOW: CFM 225 400 675 900 1,450 2,200 3,000 4,500 3,800 4,000 5,400 1,400 75 CFM/FT 68 CFM/FT <br /> MAX SP: IN WG 0.06 0.06 0.06 0.06 0.06 0.07 0.07 0.08 0.08 0.1 0.08 0.05 0.05 0.05 925 Fourth Ave.,Suite 2400 <br /> MAX CORE VEL: FPM 400 450 500 500 500 600 600 800 800 1,000 700 500 - - Seattle,Washington 98104 <br /> DEFLECTION: DEG 22.5 22.5 22.5 22.5 22.5 22.5 22.5 0 0 0 0 23 15 0 <br /> MAX NC: [2] 10 11 12 15 16 23 24 33 33 39 31 15 24 15 (PHI 206 623 9414 <br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS (FAX)206 623 7868 <br /> MODEL 272RS 272RS 272RS 272RS 272RS 272RS 272RS 272RS 272RS 272RS 272RS 272RS CT581 CT580 <br /> NOTES [4] [4, 5] Consultants <br /> NOTES: <br /> LIFE SAFETY <br /> 1. PROVIDE GRILLES WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT CEILING SYSTEMS, REFER TO ARCHITECTURAL DRAWINGS. ROLF JENSEN&ASSOCIATES <br /> 2. NC BASED ON OCTAVE BANDS 2 - 7 SOUND POWER LEVELS MINUS A ROOM ABSORPTION OF 10 DB, MEASURED PER ASHRAE 70-91. 19125 North Creek Parkway Suite 120 <br /> 3. DUCT CONNECTION AS SCHEDULED UNLESS OTHERWISE NOTED ON DRAWINGS. Bothell,Washington 98011 <br /> 4. PROVIDE HEAVY DUTY FLOOR MOUNTING BRACKET. <br /> 5. PROVIDE CONTINUOUS LENGTHS AS INDICATED. PROVIDE BLANK OFF PLATES FOR INACTIVE SECTIONS. CIVIL ENGINEER <br /> Magnusson Klemencic Associates <br /> 1301 Fifth Avenue,Suite 3200 <br /> Seattle,Washington 98101-2699 <br /> LANDSCAPE ARCHITECT <br /> CEILING DIFFUSERS Site Workshop927 Post Alley <br /> MARK CD1 CD2 CD3 CD4 CD5 CD6 CD7 CD8 Seattle,Washington 98101 <br /> TYPE DESCRIPTION MOD CORE MOD CORE MOD CORE MOD CORE MOD CORE SQUARE MOD CORE MOD CORE STRUCTURAL ENGINEER <br /> MATERIAL STEEL STEEL STEEL STEEL STEEL ALUM ALUM ALUM Magnusson Klemencic Associates <br /> NOM FACE SIZE: IN 24x24 24x24 24x24 24x24 24x24 13x13 15x15 17x17 1301 Fifth Avenue,Suite 3200 <br /> FINISH / COLOR WHITE WHITE WHITE WHITE WHITE WHITE WHITE WHITE Seattle,Washington 98101-2699 <br /> BORDER TYPE [1] [1] [1] [1] [1] [1] [1] [1] <br /> CAPACITY MAX FLOW. CFM 150 300 450 600 800 150 300 450 MECHANICAL ENGINEER <br /> NECK SIZE: IN 8x8 10x10 12x12 14x14 16x16 8x8 10x10 12x12 CDi Engineers <br /> 19203 36th Ave.W,Suite 200 <br /> DUCT CONN DIA: IN 8 10 12 14 16 8 10 12 Lynnwood,Washington 98036 <br /> MAX NECK VEL: FPM 400 500 450 600 600 400 500 450 <br /> MAX SP: IN WG 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 ELECTRICAL ENGINEER <br /> MAX NC: [2] 15 15 20 25 30 15 15 20 SPARLING <br /> 720 Olive Way,Suite 1400 <br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS TITUS TITUS TITUS TITUS Seattle,Washington 98101-1853 <br /> MODEL MCD MCD MCD MCD MCD MCD MCD MCD <br /> NOTES [3] [3] [3] [3] [3] [3] [3] [3] GENERAL CONTRACTOR <br /> MARK CD9 CD10 CD11 CD12 CD13 CD15 CD16 CD17 CD18 M.A.Mortenson Company <br /> TYPE DESCRIPTION SQUARE SQUARE LAMINAR LAMINAR LAMINAR SQUARE SQUARE SQUARE SQUARE 14719 N.E.29th Place <br /> Bellevue,Washington 98007 <br /> MATERIAL ALUM STEEL STAINLESS STAINLESS STAINLESS STEEL STEEL STEEL STEEL <br /> NOM FACE SIZE: IN 19x19 24X24 24x24 36x24 48x24 13x13 15x15 12x12 17x17 <br /> FINISH / COLOR WHITE WHITE STAINLESS STAINLESS STAINLESS WHITE WHITE WHITE WHITE Revisions <br /> BORDER TYPE [1] [1] STAINLESS STAINLESS STAINLESS [1] [1] [1] [1] <br /> CAPACITY MAX FLOW: CFM 600 1,000 150 225 300 150 300 225 450 <br /> NECK SIZE: IN 14x14 18x18 7 8 10 8x8 10x10 12x12 12x12 DOCUMENT RELEASE 09 11/03/08 <br /> DUCT CONN: IN 14 16 7 8 10 8 10 8 12 <br /> MAX NECK VEL: FPM 600 800 600 400 400 400 500 400 450 DOCUMENT RELEASE 11 02/09/09 <br /> MAX SP: IN WG 0.05 0.05 0.11 0.05 0.05 0.05 0.05 0.05 0.05 DOCUMENT RELEASE 13 03/09/09 <br /> MAX NC: [2] 25 26 24 25 25 15 15 20 20 <br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS PRICE PRICE PRICE TITUS TITUS TITUS TITUS CLARIFICATION 01/21/10 <br /> MODEL MCD MCD LFDSS LFDSS LFDSS MCD MCD SG-TDC MCD <br /> NOTES [3] [3] [4] [4] [4] [3] [3] [1, 5] [3] <br /> NOTES: <br /> 1. PROVIDE DIFFUSERS WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT CEILING SYSTEMS. REFER TO ARCHITECTURAL PLANS. <br /> 2. NC BASED ON OCTAVE BANDS 2 - 7 SOUND POWER LEVELS MINUS A ROOM ABSORPTION OF 10 DB, MEASURED PER ASHRAE 70-91. <br /> 3. PROVIDE ATTACHED PLENUM SEE DETAIL 7 ON M9.04. <br /> 4. ALUMINUM HOUSING, HINGED STAINLESS STEEL FACE GRILLE QUARTER TURN FASTENERS, STAINLESS STEEL BORDER TRIM, BUTTERFLY DAMPER ADJUSTABLE <br /> FROM FACE, SP PORT. <br /> 5. MEDIUM SECURITY. <br /> LINEAR DIFFUSERS AND EXHAUST CLOSEOUT PRINTING 04/01/12 <br /> MARK LD1 LD2 LE1 LE2 <br /> TYPE DESCRIPTION SLOT SLOT SLOT SLOT <br /> SLOTS: [1] 2 3 3 4 Drawing Title <br /> SLOT WIDTH: IN 1 1 1 1 EQUIPMENT SCHEDULES <br /> LENGTH: FT 4 4 4 4 <br /> BORDER TYPE [2] [2] [2] [2] <br /> CAPACITY INLET SIZE: IN [5] 8 10 10 12 <br /> MAX FLOW: CFM 200 360 360 500 <br /> MAX SP: IN WG 0.06 0.06 0.05 0.05 <br /> MAX NC: [3] 23 25 16 18 <br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS <br /> MODEL ML-39 ML-39 MLR-39 MLR-39 <br /> NOTES [4] [4] [4, 6] [4, 6] <br /> NOTES: , 9 D.-ko, <br /> 1. TOTAL NUMBER OF SLOTS, DIVIDED THROW EACH DIRECTION. i <br /> 0,0 ,2. PROVIDE DIFFUSERS WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT CEILING, WALL OR * �:,SILL SYSTEMS. REFER TO ARCHITECTURAL PLANS. . irk <br /> 3. NC BASED ON OCTAVE BANDS 2 - 7 SOUND POWER LEVELS MINUS A ROOM ABSORPTION OF 10 DB, ~°.-, Za7 , <br /> MEASURED PER ASHRAE 70-91 <br /> elO+•AL <br /> 4. SHEETMETAL PLENUM BY MECHANICAL CONTRACTOR, LD1 AND LD2 INSULATED. <br /> 5. INLET SIZE TO SLOT DIFFUSER PLENUM. <br /> 6. RETURN PERFORMANCE. <br /> Date: NOVEMBER 03,2008 <br /> Job No: S80613.01 <br /> Drawn By: CD <br /> Checked By: Fl <br /> Drawing No. <br /> M 0 <br /> •0 9 <br /> SHEET ISSUED FOR REFERENCE <br /> 1700 13th St-PGMC 2"Floor Surgery-B1406-017 <br />